Certification
Siemens Aktiengesellschaft
Industry Automation
Industrielle Kommunikation SIMATIC NET
Postfach 4848
D-90327 Nuernberg
Germany
You will find the EC Declaration of Conformity for this product on the Internet at the following
address:
10805878 (http://support.automation.siemens.com/WW/view/en/10805878) → tab "Entry list"
Filter settings:
Entry type: "Certificates"
Certificate Type: "Declaration of Conformity"
Search items(s): <name of the module>
ATEX approval
Certificate no.: KEMA 03ATEX1229X, type of protection 'n'
Classification: II 3 G Ex nA II T4, Temperature range: 0 to +55°C
Applied standards:
● EN 60079-0: 2006: Potentially explosive atmosphere - general requirements
● EN 60079-15: 2005: Electrical apparatus for explosive gas atmospheres
Over and above this, the conditions in the following section must be adhered to:
Important notes on installation and commissioning (Page 43) :
FM certification
Factory Mutual Research (FM), Report No: 3038618 (2 Febr. 2010)
Certificate of Compliance, hazardous (classified) location electrical equipment:
● Class 3600:1998
● Class 3611:2004
● Class 3810: 2005
● ANSI/ISA-82.02.01: 2004
Nonincendive for:
● Class I, Division 2, Groups A, B, C, D, NI/I/2/ABCD/T4A, Ta = 55°C
● Class I, Zone 2, Group IIC hazardous (classified) indoor locations, NI/I/2/IIC/T4,
cULus- und CSA-Zulassung
cULusFile: E120869
122
Ta = 55°C