Configuration
3.4 Other options when configuring a CP 243-1
Byte offset in variable
memory
CRC section
The last two bytes of the
NDB
Structure of the NDB
Name
<op>
<cnt>
<local_buffer>
<remote_buffer>
Configuration of the read/write requests
74
Name
CRC for all NDB bytes
without the CRC section
itself
Description
Request type
Value range:
"R" for read,
"W" for write
Number of bytes to be transferred
Value range:
"1" to "212"
Address of the memory area in the
local system
Value range:
"VB0" to "VBx", where x is the
max. V address
Address of the memory area on the
communications partner
Value range:
"IB0" to "IBx", where x is the
max. input address (S7-200 /
S7-300 / S7-400)
"QB0" to "QBx", where x is the
max. output address (S7-200 /
S7-300 / S7-400)
"MB0" to "MBx", where x is the
max. bit memory address (S7-
200 / S7-300 / S7-400)
"VB0" to "VBx", where x is the
max. variable address (S7-200)
"DB0.DBB0" to "DBx.DBBy",
where x is the max DB number,
and y is the highest address in
the relevant data block within
the DB (S7-300 / S7-400)
Description
2 bytes, hex
Data format
ASCII
ASCII
ASCII
ASCII
Operating Instructions, 03/2012, C79000-G8976-C244-02