Siemens CP 243-1 Operating Instructions Manual page 116

S7-200 industrial ethernet
Hide thumbs Also See for CP 243-1:
Table of Contents

Advertisement

Diagnostics
5.2 Error messages of the CP 243-1
Error word
Hex
dec
16#00B7
183
16#00BB
187
16#00BD
189
16#00BF
191
16#00F0
240
16#00F1
241
16#0100
256
bis
bis
16#0108
264
16#8080
32896
Error messages in word format
116
Description
The administrator password is
too short.
Bad IDB format
Initialization of the file system
failed
System files could not be set
up in the file system
The S7-200 CPU failed to
recognize the CP 243-1
The address of the output
byte via which the CP 243-1
is supposed to be accessible
according to the configuration
is not compatible with the
current position of the CP
243-1 in the S7-200 system.
Timeout on the S7 bus
CP 243-1 not yet completely
started up.
Reaction/remedy
Create configuration
with STEP 7 Micro/WIN
32
Create configuration
with STEP 7 Micro/WIN
32
Delete files from the file
system
Delete files from the file
system
Check configuration
and structure of the S7-
200 system
Check configuration
and structure of the S7-
200 system
Automatic restart
If necessary, check 24
V supply
Operating Instructions, 03/2012, C79000-G8976-C244-02
Transfer mechanism
Byte offset in the
Return value
SM area
(ETHx_)
20, 21
_CTRL
20, 21
_CTRL
20, 21
_CTRL
20, 21
_CTRL
_CTRL
_CTRL
20, 21
_CTRL
20, 21
_CTRL
CP 243-1