Diagnostics
5.2 Error messages of the CP 243-1
5.2.2

Error messages in word format

Error word
Hex
dec
16#0001
1
16#000D
13
16#0030
48
16#0031
49
16#0032
50
16#0033
51
16#0034
52
16#0035
53
16#0036
54
16#0038
56
16#003A
58
16#003B
59
114
Description
Timeout on the S7 bus
All data transfers are aborted
because a new configuration
was triggered by the user
program.
The configuration could not
be called up by the CPU
within the time specified.
No CDB configuration with
correct syntax found in the
memory of the S7-200 CPU
The CRC checksum of the
configuration data (CDB,
NDB, IDB) is incorrect
The configuration data for the
CP 243-1 contains errors or is
not stored correctly.
The pointer to the CDB is
wrong or no CDB is loaded
The format identifier of the
transferred configuration is
invalid
TSAPs are not unique in the
configuration or exist more
than once
The configuration is not
unique (IP addresses are
incorrect, neither clients nor
servers are configured,
channel for STEP 7
Micro/WIN 32 not activated)
The module name for the CP
243-1 was changed in the
configuration.
The configuration has an
invalid IP address
Reaction/remedy
Automatic restart
Restart of the system
Automatic restart
Check the configuration
Reconfiguration of the
CP 243-1 with STEP 7
Micro/WIN 32
Check the user program
to find out whether
configuration data was
accidentally overwritten
Reconfiguration of the
CP 243-1 with STEP 7
Micro/WIN 32
Make sure that the
ETHx_CTRL subroutine
generated by the wizard
is called at the
beginning of the user
program.
Check the configuration
Check the configuration
Check the configuration
Check the configuration
Check the configuration
Operating Instructions, 03/2012, C79000-G8976-C244-02
Transfer mechanism
Byte offset in the
Return value
SM area
(ETHx_)
20, 21
_CTRL
20, 21
_CTRL
20, 21
_CTRL
20, 21
_CTRL
20, 21
_CTRL
20, 21
_CTRL
20, 21
_CTRL
20, 21
_CTRL
20, 21
_CTRL
20, 21
_CTRL
20, 21
_CTRL
20, 21
_CTRL
CP 243-1

Advertisement

Table of Contents

   Also See for Siemens CP 243-1

   Related Manuals for Siemens CP 243-1

Comments to this Manuals

Symbols: 0
Latest comments: