Settings Required For The Mail Receive Function - Omron CS CJ1W-ETN21 Operation Manual

Sysmac cs and cj series ethernet units construction of applications
Hide thumbs Also See for CS CJ1W-ETN21:
Table of Contents

Advertisement

Using the Mail Receive Function
3-3-2

Settings Required for the Mail Receive Function

CX-Programmer
Unit Setup Tab
SMTP
Server specification type Required.
IP Address
Host name
Port No.
Local mail address
Use POP before SMTP
POP
Server specification type Required.
IP Address
Host name
Port No.
Account Name
Mail password
Server access interval
time
DNS
IP Address
(See note.)
Port No.
Retry timer
Receive Mail
Mail address
Receive file with speci-
fied extension only
Receive specified com-
mands only
Note
The following Unit settings must be made when using the Mail Receive Func-
tion.
Setting
One or the other is required, depending on the
Server specification type setting.
Rarely required (when a setting other than the
default setting of 25 is required).
Required.
Required when the account must be authenti-
cated with POP3 before sending mail.
One or the other is required, depending on the
server specification method setting.
Rarely required (when a setting other than the
default setting of 110 is required).
Required when the account name is different
from the name up to the @ symbol in the e-mail
address. (9 characters max.)
Required. (8 characters max.)
Optional (Change when the default setting of 5
minutes is unacceptable.)
Required.
Rarely required (when a setting other than the
default setting of 53 is required).
Optional (Change when the default setting of 10
seconds is unacceptable.)
Select the Protect using mail address Option
when you do not want to receive mail from
addresses other than the specified address.
Select this option when you do not want to
receive attached files other than the specified
types.
Select this option when you want to specify the
remote mail commands that can be received.
Make DNS settings when the Server specification type is set to Host name in
the SMTP or POP Tab.
Setting requirement
Section 3-3
Reference
1-4 Common Proto-
col Settings
page 40
39

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cs cs1w-etn21Sysmac cs1w-etn21Sysmac cj1w-etn21

Table of Contents