Calibrate Ch1 0V; Calibrate Ch1 10V - Omega FC-21 User Manual

Flow computer
Table of Contents

Advertisement

Sub-menus
8.2.10

Calibrate ch1 0V

Calibrate CH1 0V
Vin=TB1-2
Submenu Group
Calibrate ch1
Calibrate ch1 0V
Calibrate ch1 0V
Iin=TB1-2
8.2.11
Calibrate ch1

Calibrate CH1 10V

Iin=TB1-2
Submenu Group
Calibrate ch1
Calibrate ch1
Calibrate ch1
Iin=TB1-2
Display
GND=TB1-4
ENTER
0 CALIBRATING ——
*** DONE ***
GND=TB1-4
STOP
GND=TB1-4
ENTER
0 CALIBRATING ——
*** DONE ***
GND=TB1-4
STOP
Advance to
Calibrate ch2
To Calibrate: Connect Voltage Source (+)
TB1-2, (-) TB1-4. Input 0V and press Enter.
This message is displayed during calibration.
0V
This message is displayed when the 0V
calibration is finished.
The display will automatically return to the
Calibrate CH1 0V submenu. Press the Down
arrow key to advance to the CH1 10V
calibration.
To Calibrate: Connect Voltage Source (+)
10V
TB1-2, (-) TB1-4. Input 10V and press Enter.
This message is displayed during calibration.
10V
10V
This message is displayed when the 10V
calibration is finished.
The display will automatically return to the
Calibrate CH1 10V submenu. Press the
10V
Down arrow key to advance to the CH2 0V
calibration.
0V
49