Sub-menus
6.4.14

SETUP ANALOG OUTPUT

SETUP
ANALOG OUTPUT
ANALOG OUTPUT USAGE
Rate Total Temp Dens
ANALOG OUT FLOW TYPE
Vol
ANALOG OUTPUT RANGE
4-20mA
LS ANALOG OUTPUT
FS ANALOG OUT 20mA
ANALOG OUT DAMPING
6.4.15

SETUP RELAYS

SETUP RELAYS
Rly1 Rly2
(Relay 1 & Relay 2)
NOTE:
RELAY 1
In Batch mode,
RATE
Relay 1 is reserved
for Preset,
Relay 2 is reserved
for Prewarn.
RELAY 1 DELAY
RELAY 1 MODE
LO_ALARM
RELAY 1 DURATION
RELAY 1 SETPOINT
RELAY 1 HYSTERESIS
Display
ENTER
ENTER
CVol/Mass
ENTER
0-20mA
ENTER
####### gal/m
ENTER
####### gal/m
ENTER
0.0
ENTER
Advance To
SETUP RELAYS
Rly3 Rly4
ENTER
USAGE
TOTAL
NA
ENTER
sec
0
ENTER
HI_ALARM
ENTER
#####
ENTER
####### gal
ENTER
##### gal/m
ENTER
Advance To
SETUP RELAYS 3, 4
Press ENTER when Analog is flashing to
setup the Analog Output.
Select the desired Analog Output Usage.
Only if Rate selected & Flow EQ. = Mass, Cor/Vol
Select the desired Analog Output Flow.
Select the desired current range for the Analog
Output.
Enter desired Analog Output Low Scale Value.
NOTE: Units label will correspond with output
usage type selected.
Enter desired Analog Output Full Scale Value.
Enter the desired Analog Output Damping
Constant.
Select the desired Relay for setup.
(Relays 3 & 4 Optional)
If Relay 1 or Relay 2 Selected,
Select Rate, Total or NA.
If Rate selected, enter desired relay activation
delay value.
Select the desired Relay Activation.
Low: Relay activates when reading is below
setpoint.
High:Relay activates when reading is above
setpoint.
If Total Selected, Enter desired Relay
Duration.
Enter the desired Setpoint. The Setpoint can
be edited in run mode using the PRE 1 key
(PRE 2 key for Relay 2).
If Rate, selected, Enter desired Relay
Hysteresis.