Setup Sub-Menus; Select Ez Setup; Instrument Type - Omega FC-21 User Manual

Flow computer
Table of Contents

Advertisement

FC-21 Flow Computer
Sub-menus
6.4.1

SELECT EZ SETUP

SELECT EZ SETUP
6.4.2

INSTRUMENT TYPE

INSTRUMENT TYPE
Rate/Tot
INSTRUMENT TYPE
Rate/Tot
SELECT FLOW EQUATION
INSTRUMENT TYPE
Batch
INSTRUMENT TYPE
Rate/Tot
BATCH COUNT MODE
Up
MAXIMUM BATCH PRESET
BATCH OVERRUN COMP
Off
AUTO BATCH RESTART
Off
TIME DELAY (1-99sec)
FLOW SIGNAL TIMEOUT
MAXIMUM DRAIN TIME
SLOW START QUANTITY
SELECT FLOW EQUATION

6.4 Setup Sub-Menus

Display
STOP
START
Advance To
INSTRUMENT TYPE
ENTER
Batch
STOP
ENTER
START
Advance To
ENTER
Batch
STOP
ENTER
START
STOP
ENTER
START
1000.0 gal
STOP
ENTER
START
STOP
ENTER
START
STOP
ENTER
START
ENTER
ENTER
ENTER
ENTER
Advance To
Refer to page 20 for EZ Setup routine.
Press the DOWN (stop) key to advance to
Instrument Type. Press the UP (start) key to
advance to Administrative Setup.
Press ENTER to enter Instrument Type sub-
menus.
Press ENTER when Rate/Total is flashing to
configure the instrument as a Ratemeter/
Totalizer.
If Rate/Tot selected, advance to Select Flow
Equation.
Press ENTER to enter Instrument Type sub-
menus.
Press ENTER when Batch is flashing to
configure the instrument as a Batcher.
Select UP to Reset to 0 and count up to preset.
Select DOWN to reset to Preset and count
down to 0.
Down
Enter the maximum allowable Batch Preset.
The operator will not be able to enter a batch
preset larger than this value.
Select ON to set the unit to operate using a
Batch Overrun Compensation routine.
Select OFF to inhibit Batch Overrun
On
Compensation routine. (See Section 5.4)
Select On to enable the Auto Batch Restart. This
will automatically restart the unit at the end of
On
each batch run. Select Off if this is not desirable.
Enter Time Delay for Auto Batch Restart.
When a batch is completed, the next batch will
10
start after the amount of time entered here.
Enter a timeout of 0 to 99 seconds. If a batch is
"Filling" and zero flow persists for more than this
10
time, the batch will be aborted.
Enter time (0-99 sec.) for Max. Drain Time. After batch
quantity is reached, "Batch Done" is declared when the
10
flow rate is "0" or the Maximum Drain Time has expired.
Enter a quantity for a Slow Start up. RLY 2
(slow flow) will energize for Slow Start and RLY
10
1 (fast flow) will energize after the Slow Start
Quantity has been delivered.
22
Notes