Getting The Current Settings And Values - Siemens SINAUT MD720-3 System Manual

Gprs/gsm-modem
Hide thumbs Also See for SINAUT MD720-3:
Table of Contents

Advertisement

6.2

Getting the current settings and values

Connect your PC to the interface X1 and start a terminal software, e.g.
HyperTerminal. Select the used COM interface of the PC and configure the
character format and the baudrate to the same settings as the X1 interface of the
SINAUT MD720-3.
By factory default the SINAUT MD720-3 has the following settings:
Baudrate
Character format
When you push the SET button (less than 2 seconds) the correct IP configuration
of the SINAUT MD720-3 is shown by the terminal software.
Assigned-IP:
Remote-Host:217.6.61.22
Destination-Port:20030
Source-Port:26863
Remote-Host2:
Destination-Port2:26862
Source-Port2:RANDOM
Server-Mode:TSC
Server-Line:LL
Server-Username:st
Server-Username2:G21
Dial-Up:GPRS
System-Time:1894
Terminal-Mode:DISABLE
Firmware-Version:V.1.2.0
SIM-STATUS:SIM-OK
Provider:
NetID:
APN:
Quality:99
COM-Control:DTR
COM-Baudrate:9600
COM-Format:8E1
SINAUT MD720-3
C79000-G8976-C211
9600 Bit/s (in OPC Mode) or
19200 Bit/s (in Terminal Mode)
8N1
Assigned IP address (OPC Mode)
IP address of the OPC servers (OPC Mode)
Port address of the OPC server (OPC Mode)
Own port address (OPC Mode)
Reserved
Reserved
Reserved
Reserved
Reserved
User name at the OPC server (OPC Mode)
Reserved
Reserved
System time since last restart
Active mode: Terminal mode or OPC Mode
Firmware-Version
SIM/PIN-Status
GSM-Operator
ID of the GSM-Operator
APN of the GPRS network
Receive quality (CSQ- value)
Reserved
Baudrate on X1 interface
Character format on X1 interface
Service functions
65