To connect the 1002rp DC server to power
Step
1
2
3
Copyright © 2007, Nortel Networks
.
Plug the other end into a wall receptacle or power bar.
Action
DANGER
Only qualified personnel can alter electrical connections.
Ensure the power distribution unit (PDU) is turned off
until you are instructed to turn it on.
Connect the DC power cable to the server.
Connect the other end of the DC power cable to the PDU. Use the
supplied clips and screws to secure the plugs.
The following photograph shows the keyed plug of the DC power
cable. This plug connects to the PDU:
Note: If you are not using a Nortel-supplied PDU, have a
qualified electrician connect the cable appropriately to your DC
power plant. The 1002rp uses a negative 48 V power supply,
therefore the red cable is negative (-48 V) and the black cable is
the ground (GND).
Turn on the PDU.
Nortel CallPilot
1002rp Server Hardware Installation
NN44200-300 01.01 Standard
5.0 23 February 2007
Connecting the server to power 55
—End—