8 Settings

8.13 Power limitation

Overview
Values have been set based upon country standards. If you modify these values, you will lose certification. Therefore
you should set this function only when requested by country regulations, authorities or your grid operator.
With this function you can limit the active power fed into the grid.
The power limitation set with this function relates to the value set for the Max. Power parameter in the installation settings. For a
description of the Max. Power parameter, see "8.12 Max. Power (Maximum feed-in power)", p. 83.
Example
You have set the maximum power to 80%.
If you additionally set a power limitation of 70%, the total maximum active power is calculated as
50 kW x 80% x 70% = 28 kW.
Accessing the menu
Main menu > Active/Reactive Pwr > Active Power Ctrl > Power limit
1 0 . S e p 2 0 1 4 1 5 : 3 2
S t a t u s :
O n G r i d
P o w e r :
E - T o d a y :
I n v e r t e r I n f o .
G e n e r a l S e t t i n g s
I n s t a l l S e t t i n g s
A c t i v e / R e a c t i v e P w r
F R T
W a r n i n g :
A d j . w o u l d e f f e c t
e n e r g y p r o d u c t i o n
P a s s w o r d :
* * * *
A c t i v e P o w e r C t r l
R e a c t i v e P o w e r C t r l
P o w e r L i m i t
P o w e r v s . F r e q u e n c y
P ( V )
84
Do not change this setting without prior
consultation with Delta Solar Support.
1.
When the default information is displayed, press any button to open the main menu. Oth-
erwise, repeatedly press the button
0 W
0 k W h
2.
Use the buttons
To confirm your selection, press the button
3.
The menu is protected by password 5555. Use the buttons
To confirm a digit, press the button
4.
Use the buttons
To confirm your selection, press the button
5.
Use the buttons
To confirm your selection, press the button
until the main menu is displayed.
ESC
and
to select Active/Reactive Pwr.
.
ENT
.
ENT
and
to select Active Power Ctrl.
.
ENT
and
to select Power Limit.
.
ENT
Installation and Operation Manual for RPI M6A M8A M10A inverters V1.0 2016-02-03
and
to set each digit.