5 Planning the installation

5.10 Dry contacts

The inverter supports one multi-function relay which can be used
for external alarm devices like buzzers or strobe lights.
On the display (see "8.9 Dry contacts", p. 80), the dry contacts
can be connected to one of the following events:
Event
Description
The functionality for dry contacts is
Disabled
switched off.
On Grid
The inverter has connected to the grid.
Fan Fail
The fans are defective.
Insulation
Insulation test failed.
An error, fault, or warning message
Alarm
occurred.
Error
An error message occurred.
Fault
A fault message occurred.
Warning
A warning message occurred.
Default setting for both dry contacts is "Disabled".
Cable and wire requirements
Twisted and shielded cable (CAT5 or CAT6) with 2 wires
Cable diameter: 5 mm
Wire cross section: 1 mm
The RS485 cables should be kept separate from the AC
cable and the DC cables to avoid interferences
Providing 12 V
supply power for an external alarm device
DC
Depending on the type of communication card, the inverter pro-
vides one or two sources of on-board 12 V
Source of
Supply
supply power
voltage
Communication
a)
12 V
card
b) RS485 card
12 V
1) not recommend as it is more complicated than variant a)
Check the type of communication card installed in your inverter
before you plan how to connect dry contacts and digital inputs.
32
2
power supplies.
DC
Communication card
Type 1
Type 2
not possible
DC
x
DC
Fig. 5.17:
Communication card type 1
Fig. 5.18:
Communication card type 2
x
x
1)
Installation and Operation Manual for RPI M6A M8A M10A inverters V1.0 2016-02-03
Dry contacts
Digital inputs and
External Power Off
Dry contacts
VCC
GND
Digital inputs and
External Power Off

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rpi m8aRpi m10a

Table of Contents