Connecting to a datalogger via RS485

The inverter can be connected to a datalogger via RS485, e.g.
for monitoring, changing settings or software updates.
To ensure the proper work of the data connection, consider the
following recommendation and instructions.
When you connect a single inverter
The termination resistor has to be switched on.
When you connect multiple inverters within the same PV
system
On the last inverter in the chain, the termination resistor has
to be switched on.
If your datalogger has no internal termination resistor, the
termination resistor on the first inverter in the chain has to
be switched on too.
To each inverter a different inverter ID has to be applied.
This is necessary, so that the datalogger or the maintenance
software can identify each inverter in the chain.
The baud rate has to be the same on each inverter.
Cable and wire requirements
Twisted and shielded cables with 2 solid wires.
Cable diameter: 5 mm
Wire cross-section: 1 mm
The RS485 cables should be kept separate from the AC
cable and the DC cables to avoid interferences.
Installation and Operation Manual for RPI M6A M8A M10A inverters V1.0 2016-02-03
2