Installing the UPS

3.2 Prepare for Installing Optional Cabinets or Accessories

If you are installing optional cabinets or accessories, such as a Power Distribution Module
cabinet, an input transformer, an output transformer, or a Remote Monitor Panel, you
must install conduit between each device and the UPS cabinet for wiring these options. See
Figure 3-3 for the location of the interface points within the UPS cabinet. Also, refer to the
Powerware 9315 Series 685 and 1085 Auxiliary Battery Cabinets Installation Manual for
information on installing battery cabinets.
To prepare the UPS for wiring to an input transformer, output transformer, PDM, or all:
1. Be sure the UPS is turned off and all power sources are removed. (Refer to the
2. Open the doors of the UPS.
3. Remove the stationary right side door and set it aside for later use.
4. Remove the air filters and set aside for later use.
5. Remove the lower metal access panel. Set the access panel and hardware aside for
To prepare the UPS for wiring to an RMP, Relay Interface Module, Supervisory Contact
Module, or Remote EPO:
1. Be sure the UPS is turned off and all power sources are removed. (Refer to the
2. Open the doors of the UPS.
3. Remove the air filters and set aside for later use.
4. Remove the lower metal access panel. Set the access panel and hardware aside for
NOTE A bypass neutral feeder must be supplied when the output neutral is used. If no
bypass neutral is supplied, the output neutral is to be bonded to ground through a
minimum 3/0 copper conductor.
3−4
EATON Powerware
Powerware 9315 UPS (200–300 kVA) Operation Manual for instructions.)
later use.
Powerware 9315 UPS (200–300 kVA) Operation Manual for instructions.)
later use.
9315 UPS (200–300 kVA) Installation Manual S 164201037 Rev G www.powerware.com
®