Fig B
Please ensure that the following steps are taken:
Check the gradient for drainage flow as recommended in Figure B.
Provide clearance for easy servicing and optimal air flow as shown in Figure C.
The indoor unit must be installed such that there is no short circuit of the cool discharge air with the warm return air.
Do not install the indoor unit where there is direct sunlight shining on the unit. The location should be suitable for piping
and drainage installation. The unit must be a large distance away from the door.
Fig C
Min. 400.0mm (15.75")
Max. 250mm (9.84")
Min. 300.0mm (11.81")
Utensils, Furnitures Or Built-
In Architectural Features
Must Not Protrude More
Than 250.0mm

Ceiling Type

Floor Standing Type

1-5
Min. 10.0mm (0.39")
Min. 1.0m (39.37")