Refrigerant Piping; Maximum Pipe Length And Maximum Number Of Bends; Piping Sizes (Flare Connection Type); Piping Connection To The Units - Acson 5CE 35E Installation Manual

Table of Contents

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 1

Maximum Pipe Length And Maximum Number Of Bends

When the pipe length becomes too long, both the capacity and reliability drop. As the number of bends increases, system
piping resistance to the refrigerant flow increases, thus lowering the cooling capacity, and as the result the front compressor
may become defective. Always choose the shortest path and follow the recommendation as tabulated below:
Indoor
Model
Outdoor
Maximum Length (m)
Maximum Elevation (m)
Maximum No. of Bends

Piping Sizes (Flare Connection Type)

Piping sizes are as follows:
R22
Model
SL35C/CR
Liquid (mm/in)
9.52 / 3/8
Suction (mm/in)
19.05 / 3/4
R410
Model
5SL35C/CR
Liquid (mm/in)
9.52 / 3/8
Suction (mm/in)
15.88 / 5/8
Piping Connection
Do not use contaminated or damaged copper tubing. If
any piping, evaporator or condenser had been exposed or
had been opened for 15 seconds or more, then vacuum
and purge with field supplied refrigerant. Generally do not
remove plastic, rubber plug and brass nuts from the valves,
fittings, tubing and coils until it is ready to connect suction
or liquid line into valves or fittings.
If any brazing work is required, ensure that nitrogen gas is
passed through coil and joints while the brazing work is
being done. This will eliminate soot formation on the inside
wall of copper tubings.
Cut the pipe stages by stages, advancing the blade of pipe
cutter slowly. Extra force and a deep cut will cause more
distortion of pipe and therefore extra burr.
Remove burrs from cut edges of pipes with a remover.
This will avoid unevenness on the flare face which will
cause gas leak.
Align the center of the piping and sufficiently tighten the
flare nut with fingers. Finally, tighten the flare nut with
torque wrench until the wrench clicks.
Be sure to execute heat insulation (polyurethane form with
thickness more than 15 mm).
Except the outdoor unit which is pre-charge with refrigerant
R22, the indoor unit and the refrigerant connection pipes
must be purged because the air that contain moisture
remaining in the refrigerant cycle may cause malfunction
to the compressor.

REFRIGERANT PIPING

(5)CE 35E/ER
(5)CE 40E/ER
(5)SL35C/CR
(5)SL40C/CR
45
45
25
25
10
10
SL40C/CR
9.52 / 3/8
19.05 / 3/4
5SL40C/CR
9.52 / 3/8
15.88 / 5/8
1-9

Piping Connection To The Units

Align the center of the piping and tighten the flare nut
sufficiently with fingers.
Finally, tighten the flare nut with torque wrench until
the wrench clicks.
When tightening the flare nut with torque wrench, ensure
the direction for tightening follows the arrow on the
wrench.
Pipe Size (mm/in)
6.35 (1/4)
9.52 (3/8)
12.70 (1/2)
15.88 (5/8)
19.05 (3/4)
Flare Joint
Indoor Piping
Spanar
Torque (Nm)
18
42
55
65
78
Flared Tube
Flare Nut
Torque Wrench