Toshiba MMU-AP0072H2UL Service Manual page 89

Multi type
Hide thumbs Also See for MMU-AP0072H2UL:
Table of Contents

Advertisement

Check code
Outdoor 7-segment display
Main
remote
Check code
Sub-code
controller
Duplicated
indoor address
E08
E08
E09
E10
01:
Indoor-outdoor
communication
02:
Outdoor-
E12
E12
outdoor
communication
E15
E15
00:
Overloading
01-:
No. of units
connected
E16
E16
Location
of
Description
detection
Indoor
Duplicated
unit
indoor address
I/F
Remote
Duplicated
controller
master remote
controller
Indoor
Indoor inter-
unit
MCU
communication
error
I/F
Automatic
address starting
error
I/F
Indoor unit not
found during
automatic
address setting
I/F
Too many
indoor units
connected
Error detection
System status
condition(s)
All stop
More than one indoor unit is
assigned same address.
Stop of
In two remote controller
corresponding
configuration (including
unit
wireless), both controllers are
set up as master. (Header
indoor unit is shut down with
alarm, while follower indoor
units continue operating.)
Stop of
Communication cannot be
corresponding
established/maintained upon
unit
turning on of power or during
communication.
All stop
• Indoor automatic address
setting is started while
automatic address setting
for equipment in other
refrigerant line is in
progress.
• Outdoor automatic
address setting is started
while automatic address
setting for indoor units is in
progress.
All stop
Indoor unit cannot be
detected after indoor
automatic address setting is
started.
All stop
• Combined capacity of
indoor units exceeds 125%
of combined capacity of
outdoor units.
Note:
If this code comes up
after backup setting for
outdoor unit failure is
performed, perform "No
overloading detected"
setting.
<"No overloading detected"
setting method>
Turn on SW09/Bit 2 on I/F
P.C. board of outdoor header
unit.
• More than 48 indoor units
are connected.
89
Check items (locations)
• Check indoor addresses.
• Check for any change
made to remote controller
connection (group/
individual) since indoor
address setting.
• Check remote controller
settings.
• Check remote controller
P.C. boards.
• Check for defect in indoor
P.C. board
• Perform automatic address
setting again after
disconnecting
communication cable to
that refrigerant line.
• Check connection of
indoor-outdoor
communication line.
• Check for error in indoor
power supply system.
• Check for noise from other
devices.
• Check for power failure.
• Check for defect in indoor
P.C. board.
• Check capacities of indoor
units connected.
• Check combined HP
capacities of indoor units.
• Check HP capacity
settings of outdoor units.
• Check No. of indoor units
connected.
• Check for defect in outdoor
P.C. board (I/F).