Toshiba MMU-AP0072H2UL Service Manual page 131

Multi type
Hide thumbs Also See for MMU-AP0072H2UL:
Table of Contents

Advertisement

No.
Part name
1. Detachment
Fan motor
6
1) Carry out works of Detachment of
2) Remove wires and connectors which are
NOTE :
Release the lock of the housing part and then
remove the connectors.
3) Remove the screws of the fan motor fixing
4) Remove the fan motor while supporting it with
2. Attachment
1) Mount the fan motor and the motor fixing
2) Connect the connectors as before, which
3) Carry out work of Attachment of 3 and 5 .
1. Detachment
Side cover
7
1) Carry out work of Detachment of 1 .
2) Remove screws of the side cover.
3) Slide the side cover toward discharge
2. Attachment
1) Slide the side cover toward sucking direc-
2) Attach screws to the side cover.
3) Carry out work of Attachment of
Procedure
.
5
connected from the control P.C. board to the
fan motor.
CN333 : Fan motor power supply (5P: White)
CN334 : Fan motor position detection
(5P: White)
fittings. Earth screws are tightened together.
(M5, 0.39"(10 mm), 2 pcs.))
hands so that the fan motor does not fall.
fittings, tighten it together with earth wire
and then fix them with the screws.
were removed in works of Detachment.
(One-side: M4, 0.47"(12 mm), with washer,
1 pc.))
direction to remove the side cover.
tion and mount it while inserting hooking
claw of the side cover into the square hole
at side of the main unit.
(One-side: M4, 0.47"(12 mm), with washer,
1 pc.))
and
3
Detaching direction
Attaching direction
.
1
131
Remarks
Fan motor
Fan motor fittings
Fan motor fittings
Fan motor fittings
Earth screw
Earth screw
Earth screw
Side cover
Screw
Side cover

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents