Check code
Outdoor 7-segment display
Main
remote
Check code
Sub-code
controller
L03
L04
L04
L05
No. of priority
indoor units
L06
L06
L07
L08
L08
L09
L10
L10
L20
L28
L28
Location
of
Description
detection
Indoor
Duplicated
unit
indoor header
unit
I/F
Duplicated
outdoor line
address
I/F
Duplicated
priority indoor
unit (as
displayed on
priority indoor
unit)
I/F
Duplicated
priority indoor
unit (as
displayed on
indoor unit other
than priority
indoor unit)
Indoor
Connection of
unit
group control
cable to stand-
alone indoor
unit
Indoor
Indoor group /
unit
addresses not
set
Indoor
Indoor capacity
unit
not set
I/F
Outdoor
capacity not set
Duplicated
Indoor
central control
unit
address
I/F
Too many
outdoor units
connected
Error detection
System status
condition(s)
Stop of
There is more than one
corresponding
header unit in group.
unit
All stop
There is duplication in line
address setting for outdoor
units belonging to different
refrigerant piping systems.
All stop
More than one indoor unit
has been set up as priority
indoor unit.
All stop
More than one indoor unit
have been set up as priority
indoor unit.
Stop of
There is at least one stand-
corresponding
alone indoor unit to which
unit
group control cable is
connected.
Stop of
Address setting has not been
corresponding
performed for indoor units.
unit
Stop of
Capacity setting has not been
corresponding
performed for indoor unit.
unit
All stop
Jumper wire provided on P.C.
board for servicing I/F P.C.
board has not been removed
as required for given model.
All stop
There is duplication in central
control address setting.
All stop
There are more than four
outdoor units.
96
Check items (locations)
• Check indoor addresses.
• Check for any change
made to remote controller
connection (group/
individual) since indoor
address setting.
• Check line addresses.
• Check display on priority
indoor unit.
• Check displays on priority
indoor unit and outdoor
unit.
• Check indoor addresses.
• Check indoor addresses.
Note:
This code is displayed
when power is turned on
for the first time after
installation.
Set indoor capacity. (DN =
11)
Check model setting of P.C.
board for servicing outdoor
I/F P.C. board.
• Check central control
addresses.
• Check network adaptor
P.C. board.
• Check No. of outdoor units
connected (Only up to 4
units per system allowed).
• Check communication
lines between outdoor
units.
• Check for defect in outdoor
P.C. board (I/F).