(Errors detected by IPDU featuring in SMMS-i standard outdoor unit - typical examples)
Check code
Outdoor 7-segment display
Sub-code
01: Compressor 1
F13
02: Compressor 2
03: Compressor 3
01: Compressor 1
H01
02: Compressor 2
03: Compressor 3
01: Compressor 1
H02
02: Compressor 2
03: Compressor 3
01: Compressor 1
H03
02: Compressor 2
03: Compressor 3
01: Compressor 1
P04
02: Compressor 2
03: Compressor 3
01: Compressor 1
P07
02: Compressor 2
03: Compressor 3
0 : IGBT circuit
1 : Position detection circuit error
3 : Motor lockup error
4 : Motor current detection
C : TH sensor error
P22
D : TH sensor error
E : Inverter DC voltage error
(outdoor fan)
Note: Although letters 0 to F appear
at locations indicated by " ",
please ignore them.
01: Compressor 1
P26
02: Compressor 2
03: Compressor 3
01: Compressor 1
P29
02: Compressor 2
03: Compressor 3
Note: The above check codes are examples only, and different check codes may be displayed depending on the outdoor unit configuration
(e.g. a Super heat recovery multi system). For details, see the service manual for the outdoor unit.
Display of receiving unit
TCC-LINK
Indicator light block
central control
or main remote
Operation Timer Ready
controller
Flash
display
F13
ALT
H01
H02
H03
P04
ALT
P07
ALT
P22
ALT Outdoor fan IPDU error
P26
ALT
P29
ALT
Typical fault site
Error in temperature
Temperature sensor built into indoor IGBT (TH)
sensor built into indoor
has been open/short-circuited.
IGBT (TH)
Inverter current (Idc) detection circuit detects
Compressor breakdown
overcurrent.
Compressor error (lockup) Compressor lockup is detected
Current detection circuit
Abnormal current is detected while inverter
error
compressor is turned off.
Activation of high-pressure
High-pressure SW is activated.
SW
Heat sink overheating
Temperature sensor built into IGBT (TH) detects
error
overheating.
Outdoor fan IPDU detects error.
Short-circuit protection for compressor motor
Activation of G-Tr (IGBT)
driver circuit components is activated (momentary
short-circuit protection
overcurrent).
Compressor position
Compressor motor position detection error is
detection circuit error
detected.
83
Description of error

Hide quick links: