No.
Part name
1. Detachment
Heat
14
exchanger
1) Recover refrigerant gas.
2) Remove the refrigerant pipe at indoor unit
3) Perform work of procedure 11 -1.
4) Take off screws (Ø4 × 0.31"(8mm), 3 pcs.))
5) While holding the heat exchanger, remove
2. Attachment
1) Mount parts in order, heat exchanger
NOTE)
Arrange wires as original.
2) Attach the removed connectors and wires as
3) Connect the refrigerant pipe as original, and
Procedure
side.
fixing the piping cover to remove the piping
cover.
fixing band and fixing screws (Ø4 × 0.31"(8mm),
3 pcs.)) and then remove the heat exchanger.
→ fixing band → piping cover → drain pan
→ bell mouth → electric parts box as original.
original.
then perform vacuuming.
Fixing band
124
Remarks
Fixing band for
heat exchanger
2 fixing screws for heat exchanger