CODE No.
00
Room temperature (During control)
01
Room temperature (Remote controller)
02
Indoor suction temperature (TA)
03
Indoor coil temperature (TCJ)
04
Indoor coil temperature (TC2)
05
Indoor coil temperature (TC1)
06
Indoor discharge temperature (TF)
08
Indoor PMV opening
0A
No. of connected indoor units
0B
Total capacity of connected indoor units
0C
No. of connected outdoor units
0D
Total capacity of outdoor units
CODE No.
U1
U2
10
20
High-pressure sensor detention pressure (Pd)
11
21
Low-pressure sensor detention pressure (Ps)
12
22
Compressor 1 discharge temperature (Td1)
13
23
Compressor 2 discharge temperature (Td2)
14
24
Compressor 3 discharge temperature (Td3)
15
25
Suction temperature (TS)
16
26
Outdoor coil temperature 1 (TE1)
17
27
Outdoor coil temperature 2 (TE2)
18
28
Temperature at liquid side (TL)
19
29
Outside ambient temperature (TO)
1A
2A
PMV1 + 2 opening
1B
2B
PMV4 opening
1C
2C
Compressor 1 current (I1)
1D
2D
Compressor 2 current (I2)
1E
2E
Compressor 3 current (I3)
1F
2F
Outdoor fan current (IFan)
CODE No.
U1
U2
50
60
Compressor 1 revolutions
51
61
Compressor 2 revolutions
52
62
Compressor 3 revolutions
53
63
Outdoor fan mode
54
64
Compressor IPDU 1 heat sink temperature
55
65
Compressor IPDU 2 heat sink temperature
56
66
Compressor IPDU 3 heat sink temperature
57
67
Outdoor fan IPDU heat sink temperature
58
-
Heating/cooling recovery controlled
59
-
Pressure release
5A
-
Discharge temperature release
Follower unit release
-
5B
(U2/U2/U4 outdoor units)
5F
6F
Outdoor unit capacity
*1 Only a part of indoor unit types is installed with the discharge temperature sensor. This temperature is not displayed for other types.
*2 When the units are connected to a group, data of the header indoor unit only can be displayed.
*3 The first digit of an CODE No. indicates the outdoor unit number.
*4 The upper digit of an CODE No. -4 indicates the outdoor unit number.
1 , 5 ... U1 outdoor unit (Header unit)
2 , 6 ... U2 outdoor unit (Follower unit 1)
*5 Only the CODE No. 5* of U1 outdoor unit (Header unit) is displayed.
Data name
Display format
1
*
Data name
Display format
Data name
Display format
0: Normal
5
*
1: Recovery controlled
5
*
5
*
0: Normal
1: Release controlled
5
*
Unit
×1
°F
[0081]=71°F(27°C)
×1
°F
×1
°F
×1
°F
×1
°F
[0075]=75°F(24°C)
×1
°F
×1
°F
×1/10
pls
[0150]=1500pulse
×1
unit
[0024]=24 units
×10
ton
[0215]=21.5ton
×1
unit
[0002]=2 units
×10
ton
[0160]=16ton
Unit
×10
psi
[4350]=435psi
×10
psi
×1
°F
×1
°F
×1
°F
×1
°F
[0075]=75°F(24°C)
×1
°F
×1
°F
×1
°F
×1
°F
×1
pls
[0500] =500pulse
×1
pls
×10
A
×10
A
[0135]=13.5A
×10
A
×10
A
Unit
×10
rps
×10
rps
[0642]=64.2rps
×10
rps
×1
mode
[0058]= 58 mode
×1
°F
×1
°F
[0075]=75°F(24°C)
×1
°F
×1
°F
[0010]=Heating recovery controlled
[0001]=Cooling recovery controlled
[0010]=Pressure release controlled
[0001]=Discharge temperature release controlled
[0100]=U2 outdoor unit release controlled
[0010]=U3 outdoor unit release controlled
[0001]=U4 outdoor unit release controlled
×10
ton
[0080]=8ton