Installer Options - Drayton LP10RF Installation & User Manual

Radio frequency controlled programmable room thermostat with domestic hot water programmer
Table of Contents

Advertisement

Installation Guide
If enabled, the start time should be set an hour earlier
than the time you want the property to reach the set
temperature.
Intelligent Start will delay that start time, by an amount
that it has calculated based on the actual and set
temperature.
As the weather becomes milder, the start time is delayed,
so that fuel is not wasted bringing the room up to
temperature earlier than necessary.
The Digistat calculates approximately 10 minutes to raise
the temperature by 1°C, up to a maximum of 6°C.
NOTE:
Intelligent Delayed Start only applies in Auto mode.
Intelligent Delayed Start default is in OFF mode.
To switch ON Intelligent Delayed Start enter the
Installer Options Menu (see Installer Options 06).
NOTE:
The Intelligent Delayed start option is not suitable for
underfloor application. Ensure Installer option 06 is
set to OFF before final commissioning for underfloor
application.
SPECIAL NOTE:
If the Intelligent delayed start feature is enabled, (Off
changed to On in Installer option 06), please inform
the end user of this feature.
The following special note has been added to the user
instruction to explain the adjustment requirement:
When the delay period is operating indicated by the
flame symbol flashing, pressing any button returns the
Digistat to auto mode allowing normal button operation
until the next time/ temperature event, when it will
resume the delay start mode or follows the Holiday,
Manual, Override or Off modes as selected.
LP10RF & DIGISTAT+2RF
Client
Artworker
Creative Director
Modification Date
Changes to the installer options and pre-set programmes
must be made with the flame symbol not flashing.
Option 10 - Valve Protection
In some heating systems there may be a requirement to
protect the system by operating it once a day, for a given
period.
If valve protection is selected the system will be operated
for a period as shown in valve protection time (mins).
Valve protection time is every day at 10.00am. Valve
protection default is OFF.
To enable the valve protection mode enter the Installer
Options Menu (Refer to Installer Option 10).
Option 11 - Valve Protection time (mins).
Valve protection time can be set between 1 and 5 minutes
(default 3 minutes).
To change this once a day on time enter the Installer
Options Menu (Refer to Installer Option 11).
Option 12 - Application Type
Digistat+2RF can be used for different applications.
In the installer menu, select:
00 = Gas Boiler
0 1 = Oil Boiler
Option 13- System Capability
Adjust this setting to suit the heating system capability.
In the installer menu, select:
00 = Fast – the house usually reaches setpoint in ‹ 1 hour
0 1 = Slow – the house usually reaches setpoint in › 1 hour
Display Error code E1
When the display shows an error code (E1) this indicates
a sensor fault and the heating system will remain Off.
Please contact your local heating service engineer to
replace your Digistat +2RF.
Drayton
File Name
7542 Drayton LP10RF & DIGISTAT+2RF 06515086001 ISSC
-
PRINT
Mike Lane
Proof Stage
21/08/15 2:56PM
DIGISTAT+2RF
Finished Size
A5 148x210mm
Artwork %
100%
Bleed
3mm
9

Advertisement

Table of Contents
loading

This manual is also suitable for:

Digistat+2rf

Table of Contents