7 Functions 3

7-1 External Temperature Interlock

To use external temperature interlock, click [Function 3] on the menu, and then click [External Temperature
Interlock]. Air conditioning group can be set for this control.
By setting this control on the air conditioning unit at an entrance, our physical shock (heat shock) caused by
the extreme temperature difference can be reduced when entering into a building.
Note: If PAC-YG50ECA Expansion Controllers are connected, Expansion Controller system selection buttons will appear. Select
the desired Expansion Controller (EC1, EC2, or EC3), and make the settings for each system. Make the settings with the
Expansion Controllers properly connected.
Note: Connect our AI controller (PAC-YG63MCA) to measure outdoor temperature.
Note: This function works when the operation mode is [cooling] or [dry].
Note: When connecting AG-150A controllers by connecting an Expansion Controller to the system, external temperature interlock
settings should be made only on one of the AG-150A controllers.
External Temperature
Sensor
Select a sensor that measures
outside temperature.
Group number, group
name
Displays group number and
group name.
Refresh
Read setting data from AG-150A.
(1)Click external temperature sensor area to choose the sensor. The area displays [controller address +
sensor number + sensor name].
(2)Select a maximum additional temperature to the preset temperature for each air conditioning group. For
example, when [+4°C] is selected and the preset temperature is 24°C, the maximum set temperature will
rise to 28°C along with outdoor temperature rise. When [+2°C] is selected, the maximum set temperature
will rise to 26°C.
(3)After the setting, click the Save Settings button to send the setting data to AG-150A. When external
temperature interlock is active, the set temperature of air conditioning group is shown below.
36
External Temperature
35
34
33
32
31
30
29
28
27
26
25
24
23
Preset temperature
The set temperature of a
group that selects [+4°C]
Time
External Temperature
External Temperature >
Preset temperature+1.5°C
External Temperature >
Preset temperature+4.5°C
External Temperature >
Preset temperature+6.5°C
External Temperature >
Preset temperature+7.5°C
38
Expansion Controller
system selection buttons
Click to select the system to be
set.
Set temperature
variation
range
Select a maximum additional
temperature to the preset
temperature.
Save settings
Send setting data to AG-150A.
Set Temperature
Preset temperature+1°C
Preset temperature+2°C
Preset temperature+3°C
Preset temperature+4°C

Hide quick links: