7-3-1 Making the interlock settings
Up to 150 interlocking conditions from 1 through 150 can be set as follows.
(1) Set the input category and interlocking conditions.
Select the equipment for the input category and the interlocking conditions (event) according to Table
7-1.
Table 7-1 Interlocking conditions and the selection unit for each input category
INPUT CATEGORY
Group
(On/Off)
Group
(Mode)
Group
(Error/Normal)
Free Input Points
(On/Off)
Note: The events for output units are performed when the following state changes occurred on the input units.
<Examples of when the input category is set to Air-conditioner (On/Off):>
When [All On] is selected, the events are performed when the state changed from [One or more group Off] to [All On].
When [All Off] is selected, the events are performed when the state changed from [One or more group On] to [All Off].
When [One or more group On] is selected, the events are performed when the state changed from [All Off] to [One or more
group On].
When [One or more group Off] is selected, the events are performed when the state changed from [All Off] to [One or more
group Off].
(When AG-150A is powered on, even if a condition for a change in status is met, it does not count as an event.)
Note: Air conditioning units, LOSSNAY units, and DIDO controller (PAC-YG66DCA) are available for selection as the input unit
type (Group (On/Off); Group (Mode), Group (Error/Normal)).
Note: Different types of groups (air conditioning units, LOSSNAY units, or DIDO controller (PAC-YG66DCA)) cannot be
simultaneously selected as input unit types for each interlocking conditions.
Note: If Group (Mode) is selected for the input category, operation modes of the air conditioning units (Cool, Heat, Dry, Fan, Auto)
and LOSSNAY units (Heat Recovery, Auto, Bypass) will all be displayed. If an operation mode is selected that cannot be
used on the input unit (air conditioning or LOSSNAY units), interlocking conditions will not be met.
Note: Multiple inputs cannot be selected for a single interlocking condition.
Note: DIDO controller (PAC-YG66DCA) group cannot be selected as an input unit type if Group (Mode) was selected as the input
unit type.
INPUT UNIT
ICON
CONDITION 1
All Groups On
All Groups Off
One or more Groups On
One or more Groups Off
All groups in the mode
All groups out of the mode
One or more groups in the mode
One or more groups out of the mode
All units in error
All units in normal operation
One or more units in error
One or more units in normal operation
All Units On
All Units Off
One or more Units On
One or more Units Off
INTERLOCKING CONDITIONS (EVENT)
Cool, Heat, Dry
Fan, Auto
Heat Recovery (LOSSNAY),
Auto (LOSSNAY)
Bypass (LOSSNAY)
42
SELECTION
UNIT
CONDITION 2
-
Group
Group
-
Group
Unit
-
(point)