7-3 Interlock control

To use Interlock control, click [Functions 3] on the menu, and then click [Interlock control]. Interlock conditions
and actions can be set.
After the settings are made, click [Save Settings] to send setting data to AG-150A.
Input category
Use this menu to select
the input type.
Enable/Disable
interlock control
Use these buttons to enable/
disable the setback function.
Enable/Disable
Use these buttons to enable
or disable each item.
Input state
Use this menu to set the
interlocking conditions.
Select input units
Use this menu to display
the screen on which to
select input units.
Refresh button
Press this button to import the
settings from AG-150A.
.
The interlock control verifies the state changes in an ascending order of No.1 to 150 every three to five
seconds. When the conditions are met, the interlock action commands will be issued to the output units.
By registering an "Interlock Control" license for the AG-150A and making the settings for the input category,
interlocking conditions, input unit type, output category, action type, and output unit type for conditions No. 1
through 150, the operation of the equipment that are connected to AG-150A can be interlocked with the
operation of the indoor units.
Shown below are two examples of such interlocked operations.
Example1: Interlocked operation of indoor unit and window through the free contact on an indoor unit
Signal indicating the window is
AG-150A
Example 2: Interlocked operation of indoor unit, lighting, and card key through the free contact of an indoor unit
Signal indicating the card
key has been removed
AG-150A
open
Signal to stop the air
conditioning unit
The card key status signal to the
Signal to stop the air
conditioning unit and
turn off the lights.
The open/close status of the window
is input to the free contact.
Indoor unit
input point
Indoor unit
ON/OFF signal to the
lighting.
40
Output unit type
Use this menu to select the
output unit type
Edit buttons
Use these buttons to insert,
delete, clear, copy, and paste
data.
Status bar
Shows the settings status for 150
conditions (Green: Settings have
been made; Red: Incomplete
settings exist.)
Action settings
Use this menu to select the type
of interlocked actions.
Select output units
Use this menu to display the screen
on which to select output units.
Scroll bar
Use the scroll bar to go up and
down the page.
Save Settings button
Press this button to send the
settings to the AG-150A.
Window
Card key
Lighting

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Gb-50ada-aGb-50ada-j

Table of Contents