Congratulations; Sample Of Serial Number / Safety Label - Quadra-Fire 57ST-ACC Owner's Manual

5700 step top wood stove series
Hide thumbs Also See for 57ST-ACC:
Table of Contents

Advertisement

5700 STEP TOP ACC
A. Congratulations
Hearth & Home Technologies welcomes you to our tradition
of excellence! In choosing a Quadra-Fire appliance, you
have our assurance of commitment to quality, durability, and
performance.
This commitment begins with our research of the market,
including 'Voice of the Customer' contacts, ensuring we
make products that will satisfy your needs. Our Research
and Development facility then employs the world's most
NOTE: Clearances may only be reduced by means
approved by the regulatory authority having jurisdiction
B. Sample of Serial Number / Safety Label
LOCATION: Back of unit
CAUTION
ATTENTION:
LISTED ROOM HEATER, SOLID FUEL TYPE.
APPAREIL DE CHAUFFAGE DE PIÈCE, DE TYPE DE
ALSO FOR USE IN MOBILE HOMES. (UM)
COMBUSTIBLE SOLIDE, POUR USAGE DANS LES
84-HUD . "For Use with Solid Wood Fuel Only"
MAISONS MOBILES. (UM) 84 HUD. "Pour Usage Avec
Bois Solide Seulement"
PREVENT HOUSE FIRES
PRÉVENTION DES FEUX DE MAISON
Install
and
use
only
in
accordance
with
Installez et utilisez en accord avec les instructions
manufacturer's
installation
and
operating
d'installation et d'opération du fabricant. Contactez le
instructions. Contact local building or fire officials
bureau de la construction ou le bureau des incendies au
about restrictions and installation inspections in
sujet des restrictions et des inspections d'installation dans
your area. Do not obstruct the space beneath
votre voisinage. Ne pas obstruez l'espace en dessous de
heater.
l'appareil.
SUITABLE FOR MOBILE HOME INSTALLATION
CONVIENT POUR UNE INSTALLATION MAISON MOBILE
WARNING - For Mobile Homes: Do not install in
AVIS - Pour Les Maisons Mobiles: Ne pas installer dans
une chambre à coucher. Un tuyau extérieur de
a sleeping room. An outside combustion air inlet
combustion d'air doit être installé et ne doit pas être
must be provided and unrestricted while unit is in
obstrué lorsque l'appareil est en usage. La structure
use. The structural integrity of the mobile home
intégrale du plancher, du plafond et des murs de la
floor, ceiling and walls must be maintained. The
maison mobile doit être maintenue intacte. L'appareil de
stove needs to be properly grounded to the frame
chauffage doit être fixé à la charpente de la maison
of the mobile home.
Components required for
mobile. Les composants requis pour l'installation des
mobile home installation:
Outside Air Kit, Part
maisons mobiles: Assemblage d'air extérieur, Numéro de
Number OAK-ACC.
Pièce OAK-ACC.
Refer to manufacturer's instructions and local
Référez vous aux instructions du fabricant et des codes
codes for precautions required for passing
locaux pour les précautions requises pour passer une
chimney through a combustible wall or ceiling and
cheminée à travers un mur ou un plafond combustibles,
et les compensations maximums.
maximum offsets.
Inspectez et nettoyez la cheminée fréquemment. Sous
Inspect and clean chimney frequently - Under
certaines conditions, il se peut que la créosote
Certain Conditions of Use, Creosote Buildup May
s'accumule rapidement.
Occur Rapidly.
Ne pas connecter cet appareil à une cheminée servant un
Do not connect this unit to a chimney serving
autre appareil.
another appliance.
Composants Optionnels: Ventilateur Optionnel, Pièce
Optional Components:
Optional Blower, Part
BK-ACC.
BK-ACC.
Puissance Électrique: 115 VAC, 1.2 Amps, 60 Hz.
Electrical Rating: 115 VAC, 1.2 Amps, 60 Hz.
Éloignez le fil électrique de l'appareil. Ne pas faire passer
Route power cord away from unit. Do not route
le fil électrique au dessus ou en dessous de l'appareil.
DANGER: Il y a risque de décharge électrique.
cord under or in front of appliance.
Déconnectez le fil électrique de la prise de contact avant
DANGER: Risk of electrical shock. Disconnect
le service.
power supply before servicing.
Remplacez la vitre seulement avec une vitre céramique
Replace glass only with 5mm ceramic available
de 5 mm disponible chez votre fournisseur.
from your dealer.
N'élevez pas le feu. Bâtissez le feu de bois directement
Do not use grate or elevate fire. Build wood fire
sur l'âtre.
directly on hearth.
Ne pas surchauffer. Si l'appareil de chauffage ou le tuyau
Do not overfire - if heater or chimney connector
de cheminée rougissent, vous surchauffez.
glows, you are overfiring.
Opérez l'appareil seulement lorsque la porte de
chargement est fermée. Ouvrez la porte seulement
OPERATE ONLY WITH DOORS CLOSED
lorsque vous devez ajouter des combustibles dans le feu.
Open only to add fuel to the fire.
Ne mettez PAS le poêle en marche tant que tous les
Do NOT operate before fully assembling
composants n'ont pas été entièrement assemblés.
components.
ATTENTION: Seulement utilisé carburant approuvé
WARNING: Only used approved wood fuel listed
in owners manual. Burning any other fuel will void
indiquée dans le manuel des propriétaires. La
warranty.
combustion d'autres combustibles annulera la garantie.
PROTECTION DU PLANCHER:
FLOOR PROTECTION
:
Le protecteur de plancher doit être d'un minimum de 1 inch
Floor protector must be a 1 inch min. thickness, ("k" value =
(25mm) d'épaisseur, ('k" value = .49, R value = 2.04) de matériel
.49, R value = 2.04)
non-combustible material or equivalent,
incombustible ou équivalent, s'étendant du dessous de l'appareil
extending beneath heater and to front/sides/rear as indicated
de chauffage à l'avant, aux cotés et à l'arrière comme indiqué
on the diagram below. Exception: Non-combustible floor
sur le diagramme suivant. Exception: Les protections
protections must extend beneath the flue pipe when installed
incombustibles du plancher doivent s'étendre en dessous du
with horizontal venting and extend 2 inches (51mm) beyond
conduit de cheminée lorsqu'installées avec une ventilation à
each side.
l'horizontale et s'étendre de 2 inches (51mm) de chaque côté.
45-7/8"
minimum
Fuel loading door
8"
16" from glass
USA
33-5/8"
minimum
Made in U.S.A.
Manufactured by:
Fabriqué aux États-Unis-d'Amérique par
Fabriqué par:
1445 N. Highway, Colville, WA 99114
des pièces d'origine américaine et pièces
www.quadrafire.com
2
and Welcome to the Quadra-Fire Family
HOT WHILE IN OPERATION DO NOT TOUCH, KEEP CHILDREN AND CLOTHING AWAY. CONTACT MAY CAUSE SKIN BURNS. KEEP
:
FURNISHINGS AND OTHER COMBUSTIBLE MATERIAL FAR AWAY FROM THE APPLIANCE. SEE NAMEPLATE AND INSTRUCTIONS
CHAUD LORS DE L'OPÉRATION. NE PAS TOUCHER. GARDEZ LES ENFANTS ET LES VÊTEMENTS LOIN DE L'ESPACE DÉSIGNÉ DE L'INSTALLATION. LE CONTACT
PEUT CAUSER DES BRÛLURES À LA PEAU. GARDEZ LES MEUBLES ET LES MATÉRIAUX COMBUSTIBLES LOIN DE L'ESPACE DÉSIGNÉ DE L'APPAREIL. VOIR
L'ÉTIQUETTE ET LES INSTRUCTIONS.
Tested and
Portland
O-T L
Listed by
Oregon USA
C
US
OMNI-Test Laboratories, Inc.
Report / Rapport
#061-S-73-6.2
VENT SPECIFICATIONS:
SINGLE WALL: Six inch (6 inches) (152mm) diameter, minimum 24 MSG black
or blued steel connector pipe, with a listed factory-built UL103HT* Class "A"
chimney, suitable for use with solid fuels, or a masonry chimney, and the
referenced clearances.
DOUBLE WALL: Six inch (6 inches) (152mm) diameter, listed double wall air
insulated connector pipe with listed factory-built UL103HT* Class "A" chimney,
or a masonry chimney and the referenced clearances
MOBILE HOME: Use double wall pipe by Dura-Vent DVL, Selkirk Metalbestos
DS or Security DL double wall connector pipe. Must be equipped with a spark
arrestor. Apply double wall clearances below when installing unit.
MIN CLEARANCES TO COMBUSTIBLE MATERIALS: Inches & (Millimeters)
NOTE: All "A" , "C" and "F" Dimensions are to inside diameter of flue collar.
INSTALLATION: FULL VERTICAL INSTALLATION: ENTIÈREMENT VERTICALE
SINGLE WALL PIPE
DOUBLE WALL PIPE
INSTALLATION: HORIZONTAL WITH MINIMUM 2 FT VERTICAL OFF STOVE TOP
INSTALLATION: HORIZONTALE AVEC 609mm VERTICAL MINIMUM DU HAUT DU POÊLE
SINGLE WALL PIPE
DOUBLE WALL PIPE
o
INSTALLATION: 90
ELBOW OFF TOP OF STOVE THROUGH BACKWALL
o
INSTALLATION: 90
DU COURBURE AU DESSUS DE HAUT DU POÊLE A TRAVERS LE MUR ARRIERE
SINGLE WALL PIPE
DOUBLE WALL PIPE
INSTALLATION: ALCOVE - Six inch (6 inches) (152mm) diameter listed DOUBLE WALL air insulated connector pipe with UL103 HT** listed factory-built
Class "A" chimney, or a masonry chimney. (Mobile Home must be equipped with a spark arrestor.) Maximum depth of Alcove shall be no more than 48
inches (1219mm) with a minimum height of 79.25 inches (2013mm) from floor to bottom of ceiling and the referenced clearances.
INSTALLATION: ALCÔVE - De six (6 inches) (152mm) de diamètre, le connecteur du conduit d'air isolé pour mur double avec une cheminée bâtit en usine
UL103HT** de Classe "A", ou une cheminée de briques. (Les maisons mobiles doivent être équipées d'un arrêt d'étincelle). La profondeur maximum de
l'alcôve ne doit pas être de plus de 48 inches (1219mm) avec une hauteur minimum de 45 inches (1143mm) la distance entre du plancher et plafond inférieur,
et des espaces libres alloués.
203mm (8")
(**In Canada must comply with Standard CAN/ULC-S629-M87 for the 650
(**Au Canada doit conformer a CAN/ULC-S629-M87 la norme pour 650
203mm
203mm
(8")
(8")
1419mm
(55-7/8")
DOUBLE WALL PIPE
minimum
*
457mm (18")
SEE PIPE MANUFACTURERS CLEARANCES - NOT TESTED
CANADA
1092mm (43")min
of US and
2015 2016 2017 Jan. Feb. Mar. Apr. May June July Aug. Sept. Oct. Nov. Dec.
imported parts.
DO NOT REMOVE THIS LABEL / NE PAS ENLEVER L'ÉTIQUETTE
importées.
advanced technology to achieve the optimum opera-
tion of our stoves, inserts and fi replaces. And yet we are
old-fashioned when it comes to craftsmanship. Each unit
is meticulously fabricated and gold and nickel surfaces are
hand-fi nished for lasting beauty and enjoyment. Our pledge
to quality is completed as each model undergoes a quality
control inspection.
We wish you and your family many years of enjoyment in
the warmth and comfort of your hearth appliance. Thank
you for choosing Quadra-Fire.
R
5700 Step Top ACC
TESTED TO:/ TESTÉ À:
UL 1482-96, ULC S627-00
MUR SIMPLE: De six (6 inches) (152mm) de diamètre le connecteur de conduit de
minimum d'acier noir ou bleu de minimum de 24MSG, avec une cheminée bâtit en usine
UL103HT* de Classe "A", adéquate pour usage avec les combustions solides, ou une
cheminée de briques, avec espaces libres référés.
MUR DOUBLE: De six (6 inches) (152mm) de diamètre, le connecteur du conduit d'air
isolé pour mur double avec une cheminée bâtit en usine UL103HT* de Classe "A:, ou
une cheminée de briques, avec espaces libres alloués.
MAISON MOBILE:
Metalbestos DS ou Security DL. Doit être équipé d'un arrêt d'étincelle. Utiliser les
espaces libres pour mur double comme mentionné ci-bas.
ESPACES LIBRES MIN DES MATÉRIAUX COMBUSTIBLES:
NOTE: Toutes les dimensions "A", "C", et "F" sont à partir du diamètre intérieur
de l'entrée du conduit.
A
B
C
D
E
F
G
12.5 (318) 10.5 (267) 25.5 (648) 15 (381) 2 (51) 12 (305) 45 (1143) N/A
9.5 (241) 7.5 (191) 25.5 (648) 15 (381) 2 (51) 12 (305) 45 (1143) N/A
9.5 (241) 7.5 (191) 25.5 (648) 15 (381)
*
*
45 (1143) 18 (457) *
9.5 (241) 7.5 (191) 25.5 (648) 15 (381)
*
*
45 (1143) 13 (330)
9.5 (241) 7.5 (191) 25.5 (648) 15 (381) 2 (51) 12 (305) 45 (1143) 18 (457)*
9.5 (241) 7.5 (191) 25.5 (648) 15 (381) 2 (51) 12 (305) 45 (1143) 13 (330)
o
C Factory-built chimney.)
o
C cheminée bâtit en usine.)
10.5 (268) 8.5 (216) 25.5 (648) 15 (381) N/A
N/A
45 (1143)
particulate emission standards at 2.3 G/HR EPA Methods 28 and 5G. Not approved for
proper operation. Consult the owner's manual for further information. It is against federal
7038-207E
!
SERIAL NO. NUMÉRO DE SÉRIE
007009
SPÉCIFICATIONS DE LA VENTILATION:
Utiliser un conduit de mur double par Dura-Vent DVL, Selkirk
En Pouces & (millimètres)
A
BACKWALL/SIDE
WALL/
H
MUR
ARRIÈRE/MUR
CONDUIT DU MUR SIMPLE
DE CÔTÉ
CONDUIT DU MUR DOUBLE
CORNER
E
INSTALLATION/
INSTALLATION
DU COIN
CONDUIT DU MUR SIMPLE
CONDUIT DU MUR DOUBLE
G
ALCOVE SIDE
VIEW /
VUE DE CÔTÉ
DE L'ALCÔVE
CONDUIT DU MUR SIMPLE
CONDUIT DU MUR DOUBLE
ALCOVE TOP
VIEW /
VUE DU HAUT DE
L'ALCÔVE
90 OFF TOP UP & OUT
CEILING CLEARANCE/
G
ESPACE LIBRE DU
DESSUS DE
L'APPAREIL AU
PLAFOND AVEC 90 DE
COURBURE
*
STOVE TO CEILING CLEARANCE/
ESPACE LIBRE DU POÊLE AU
PLAFOND
U.S. ENVIRONMENTAL PROTECTION AGENCY Certified to comply with 2015
sale after May 15, 2020. This wood heater needs periodic inspection and repair for
regulations to operate this wood heater in a manner inconsistent with the operating
instructions in the owner's manual.
Serial No.
Model
Name
B
C
Test Lab &
D
Report No.
F
E
F
A
B
C
D
H
Mfg. Date
7038-162G
February 25, 2016