Sensor operating temperature
Receiver operating temperature
Storage temperature
Storage and operating humidity range
Accuracy
Resolution
Setpoint functional range (WDS only)
Receiver voltage
Receiver power consumption
Housing
Mounting
Sensor battery
Range
Output power
Radio frequency
Radio channels
Address range
Minimum time between transmissions
Maximum time between transmissions
(a) Range values are estimated transmission distances for satisfactory operation. Actual distance is job specific and must be
UNT-SVX07B-EN
(a)
determined during site evaluation.
32ºF to 122ºF (0ºC to 50ºC)
-40ºF to 158ºF (-40ºC to 70ºC)
-40ºF to 185ºF (-40ºC to 85°C)
5% to 95%, non-condensing
0.5°F over a range of 55ºF to 85°F (12.8ºC to 29.4°C)
0.125ºF over a range of 60ºF to 80ºF (15.56ºC to 26.67°C)
0.25ºF when outside this range
50ºF to 89.6ºF (10ºC to 32ºC)
24 V nominal ac/dc ±10%
<1 VA
Polycarbonate/ABS blend, UV protected, UL 94-5VA
flammability rating, suitable for application in a plenum
3.24 in (8.26 cm) for 2 mounting screws (supplied)
(2) AA, 1.5 V, 2800 mAh, lithium, 5-year life, UL listed
Open range: 2,500 ft (762 m) (packet error rate = 2%)
Usable: 200 ft (61 m)
Typical: 75 ft (23 m)
100 mW
2.4 GHz (IEEE Std 802.15.4-2003 compliant)
(2405 to 2480 MHz, 5 MHz spacing)
16
000 to 999
30 seconds
15 minutes