Trane 20-80 ton water-cooled air conditioners 20-60 ton air-cooled air conditioners remote air-cooled condensers manual pkg-prc002-en intellipak signature series (101 pages)
Control panel *Featured on fan-coils only Figure 1. Main components of a fan-coil or cabinet heater unit. UNT-IOM-6 General Information Hydronic coil *Main drain pan Supply fan(s) Fan motor(s) Piping package Throwaway filter *Auxiliary drain pan...
Model A Vertical Concealed Model C Horizontal Concealed Model E Horizontal Recessed Cabinet Styles Model D Horizontal Cabinet Model F Wall Hung Cabinet** Model B Vertical Cabinet UNT-IOM-6...
Page 5
Model H Vertical Recessed Model K Low Vertical Concealed* Model M Inverted Vertical Cabinet** *Fan-coil only **Force Flo cabinet heater only UNT-IOM-6 Model J Vertical Slope Top Cabinet Model L Low Vertical Cabinet* Model N Inverted Vertical Recessed**...
Page 6
Model Number Description Figure 2. The unit nameplate is on the fan scroll. UNT-IOM-6...
UNT-IOM-6 Installation Checklist WARNING: Allow rotating fan to stop before servicing equipment. Failure to do so may cause severe personal injury or death. CAUTION: The unit must be installed level (zero tolerance) in both horizontal axis for proper operation. Failure to do so may result in condensate management problems such as standing water inside the unit.
Vertical Units Figure 4. Keyslot Hanger Hole Locations UNT-IOM-6 Installing the Unit CAUTION: Do not allow electrical wire to fall between the unit and installation surface. Failure to comply may cause electrical shorts or difficulty in access- ing wires.
Horizontal Units CAUTION: All unit panels and filters must be in place prior to unit start-up. Failure to have panels and filters in place may cause motor overload. UNT-IOM-6...
Page 18
· · · · · · CAUTION: All unit panels and filters must be in place prior to unit start-up. Failure to have panels and filters in place may cause motor overload. UNT-IOM-6...
Page 19
Figure 5. Trim ring assembly installation. UNT-IOM-6...
Page 21
Units with Hydronic Coil Connections Only Piping Considerations UNT-IOM-6 Piping · · · · CAUTION: When using a field supplied piping package in a fan-coil unit, allow sufficient room to install the auxiliary drain pan. In addition, piping package must not extend over edges of auxiliary drain pan.
Page 22
Units with Steam Coils CAUTION: In all steam coil installations, the con- densate return connections must be at the low point of the coil to ensure condensate flows freely from the coil at all times. Failure to do so may cause physical coil damage from water hammer, unequal thermal stresses, freeze-up and/or corrosion.
Page 23
ST = Strainer FT = Float and thermostatic steam trap MV = Manual air vent GV= Gate valve VB = Vacuum breaker, 15° swing check valve Figure 8. Example of typical piping to the steam coil. UNT-IOM-6...
Page 24
Factory Piping Package Connections Piping Considerations · · · · Figure 9. Remove the shipping brackets which support the factory piping package before connecting piping. UNT-IOM-6...
Installing the Auxiliary Drain Connecting the Condensate Drain UNT-IOM-6 Figure 10. Insert the auxiliary drain pan tabs into these slots in the fan-coil chassis end panel. Figure 11. The horizontal auxiliary drain pan in its installed position.
Condensate Overflow Detection Device Automatic Changeover Sensor Figure 12. Condensate overflow switch installed in a vertical auxiliary drain pan. Figure 13. Condensate overflow switch installed in a horizontal auxiliary drain pan. UNT-IOM-6...
Page 27
Automatic Electric Heat Lockout Switch (Fan-coil) UNT-IOM-6 Figure 14. The changeover sensor strapped to the supply water pipe. ° Figure 15. Units with electric heat have an electric heat lockout switch on the supply water pipe.
Venting the Hydronic Coil Figure 16. The hydronic coil air vent is above the coil connections. A horizontal unit is on the left and a vertical on the right. UNT-IOM-6...
Supply Power Wiring UNT-IOM-6 Electrical Connections WARNING: Hazardous voltage! Disconnect all electric power including remote disconnects before servicing. Failure to do so may cause severe personal injury or death. · · CAUTION: Use copper conductors only! Unit terminals are not designed to accept other types of conductors.
Page 34
Figure 23. The terminal unit control (TUC) board pivots downward to provide service access. WARNING: Insulate all power wire from sheetmetal ground. Failure to do so may cause electrical shorts resulting in personal injury or death. UNT-IOM-6...
Electrical Grounding Restrictions Wall Mounted Control Interconnection Wiring UNT-IOM-6 CAUTION: Unit transformer IT1 provides power to fan-coil unit only. Field connections to the transformer IT1 may create immediate or premature unit component failure.
Page 38
Figure 25. Wall mounted zone sensor dimensions. Figure 26. Resistance temperature curve for the zone sensor, entering water temperature sensor, and discharge air sensor. Wall mounted zone sensor Split-mounted option: Model # Digit 31 = W Wall mounted setpoint dial with unit mounted fan mode switch Model # Digit 31 = X UNT-IOM-6...
Yellow COMM LED Red SERVICE LED LED Activity Red Service LED Troubleshooting Figure 28. The Tracer ZN.010 board. ® Tracer ZN.010 and ZN.510 Green STATUS LED UNT-IOM-6...
Page 47
Green STATUS LED Yellow COMM LED UNT-IOM-6 Tracer and ZN.510 · · · ® ZN.010...
Page 48
Manual Output Test Manual Output Test Procedure · · ® Tracer ZN.010 and ZN.510 UNT-IOM-6...
Page 50
® Tracer ZN.010 and ZN.510 Diagnostics UNT-IOM-6...
Page 51
Resetting Diagnostics Automatic Reset by the Controller Manual Output Test Cycling Power to the Controller UNT-IOM-6 ® Tracer ZN.010 and ZN.510...
Page 52
Trane’s Service Tool, Rover™ Alarm Reset ® Tracer ZN.010 and ZN.510 UNT-IOM-6...
Page 53
® Tracer ZN.010 and ZN.510 Troubleshooting UNT-IOM-6...
Page 82
Tracer ® ZN.520 Caution: If the Service push button is held down for more ® than 15 seconds, the Tracer ZN.520 controller will uninstall itself from the ICS™ communication network and shut down all unit operation. This mode is indicated by the red Service LED flashing once every second.
Page 87
Terminal Unit Control (TUC) ä Figure 29. The TUC module board. UNT-IOM-6...
Page 88
Tracer ® Communication Wiring Terminal Unit Control (TUC) · · · · · · · · · UNT-IOM-6...
Page 89
Service Communication Wiring Wall-Mounted Zone Sensor Module Terminal Unit Controller Start-Up UNT-IOM-6 Terminal Unit Control (TUC) · · ä ä ä ä...
Page 90
TUC Human Interface Setting the ICS Ad- dress for Tracer Com- munications Terminal Unit Control (TUC) ° · ° · ° ° ° UNT-IOM-6...
Page 92
Cooling and Heating Operation Setpoint Control TUC Sequence of Operation · · · ° ° ® Terminal Unit Control (TUC) ° UNT-IOM-6...
Page 93
Fan Mode Operation UNT-IOM-6 Terminal Unit Control (TUC) ° ä °...
Page 94
Entering Water Temperature Sampling Function 2-Pipe with Auxiliary Electric Heat (Fan-coils) · · · · · · ° ° ° ± ° Terminal Unit Control (TUC) ³ ³ ³ ³ UNT-IOM-6...
Page 95
Fresh Air Damper Options Manual Auto 2-Position Economizer UNT-IOM-6 Terminal Unit Control (TUC) Figure 30. Re-locate the damper stop screw to adjust the damper position. The factory positions the stop screw in the 25% open position. â ä...
Page 96
Terminal Unit Control (TUC) ° ° ° ° ° UNT-IOM-6...
Page 97
BIP4: Low Temperature Detection Option BIP3: Condensate Overflow Detection Device UNT-IOM-6 Terminal Unit Control (TUC) ° Figure 31. The low temperature sensor is a capillary tube inserted into the coil to detect freezing conditions. °...
Page 98
BIP4: Smoke Input BIP3: Occupied/ Unoccupied Mode BIP1: External Interlock Terminal Unit Control (TUC) â UNT-IOM-6...
Page 99
BIP2: Motion Detection Autocycle Test UNT-IOM-6 CAUTION: If the TUC is left in the autocycle test mode, it will automatically return to normal unit opera- tion after 60 minutes. Terminal Unit Control (TUC)
Page 100
¡ l ¡ l ¡ l ¡ l l ¡ ¡ l l l l ¡ ¡ ¡ l ¡ ¡ l l ¡ l ¡ l ¡ l l l l ¡ ¡ l l ¡ l l l l ¡ ¡...
Periodic Maintenance Checklist Maintenance Procedures Filters Maintenance WARNING: Allow rotating fan to stop before servicing equipment. Failure to do so may cause severe personal injury or death. UNT-IOM-6...
Page 117
CAUTION: All unit panels and filters must be in place prior to unit start-up. Failure to have panels and filters in place may cause motor overload. Table 53. Filter Sizes, in. (cm) UNT-IOM-6...
Page 118
Inspecting and Cleaning Drain Pans UNT-IOM-6...
Page 119
Auxiliary Drain Pan Main Drain Pan UNT-IOM-6 CAUTION: Exercise extreme care when removing auxiliary drain pan. Failure to do so may cause plastic mounting tabs to break. Coil Main Drain Pan Figure 32. When replacing the fan-coil’s main drain pan, install it correctly under the z-bar.
Page 120
Winterizing the Coil Figure 33. To remove the main drain pan on vertical fan-coil units, disconnect the clips holding the pan to the fanboard. Figure 34. To remove the main drain pan on horizontal fan- coil units, peel the insulation from the edges of the pan’s underside to access the mounting screws.
Page 121
Inspecting and Cleaning Coils Steam and Water Coils UNT-IOM-6...
Fan Board Assembly Removal Replacing the Motor WARNING: Allow rotating fan to stop before servicing equipment. Failure to do so may cause severe personal injury or death. CAUTION: Support the fanboard when removing it from the unit. Failure to do so may cause personal injury. Figure 35.
Page 129
For Reference Only: This schematic shows typical wiring of a fan-coil. It is not intended for a basis of design or for equipment installation purposes in the field. For an as-built schematic specific to a particular unit, please see the ship-with schematic for that specific unit.
Page 130
This schematic shows typical wiring of a fan-coil. It is not intended for a basis of design or for equipment installation purposes in the field. For an as-built schematic specific to a particular unit, please see the ship-with schematic for that specific unit or contact your local Trane representative. Two-pipe autochangeover...
Page 131
This schematic shows typical wiring of a fan-coil. It is not intended for a basis of design or for equipment installation purposes in the field. For an as-built schematic specific to a particular unit, please see the ship-with schematic for that specific unit or contact your local Trane representative. Two-pipe autochangeover with electric heat...
Page 132
This schematic shows typical wiring of a fan-coil. It is not intended for a basis of design or for equipment installation purposes in the field. For an as-built schematic specific to a particular unit, please see the ship-with schematic for that specific unit or contact your local Trane representative. Four-pipe...
Page 133
For an as-built schematic specific to a particular unit, please see the ship-with schematic for that specific unit or contact your local Trane representative. Two-pipe unit with a modulating valve Electric heat terminal unit controller Wall mounted zone sensor —...
Page 134
For an as-built schematic specific to a particular unit, please see the ship-with schematic for that specific unit or contact your local Trane representative. Four-pipe unit with control valves (both modulating) terminal unit controller Wall mounted zone sensor —...
Page 136
An American Standard Company Literature Order Number UNT-IOM-6 File Number PL-TD- UNT-IOM-6-4-00 Supersedes UNT-IOM-5 Stocking Location LaCrosse Since The Trane Company has a policy of continuous product improvement, it reserves the right to change design and specifications without notice.
Need help?
Do you have a question about the LO and is the answer not in the manual?
Questions and answers