Figure 10. Manual circuit setter valve
Figure 11. Automatic circuit setter valve
Figure 12. Automatic circuit setter valve
Perform the following procedure to set maximum water flow through the coil:
1. Establish water flow through the coil. Perform an open override of the valve if the control valve
UNT-SVX07B-EN
is closed to the coil, either manually or by Tracer.
If the piping package has two-position, normally closed valves: Drive open the valve using a
24 V signal.
If the piping package has two-position, normally open valves: Manually drive open the valve
by removing power to the valve.
Installation—Mechanical
43