Trane UniTrane Installation, Operation And Maintenance Instructions page 62

Fan-coil and air conditioners
Table of Contents

Advertisement

Installation—Electrical
Table 8.
Unit
Size
Note: Actual rpm will vary with application and configuration. Size 10 and 12 units have two motors.
Table 9.
Unit
Size
Note: Actual rpm will vary with application and configuration. Size 10 and 12 units have two motors.
Table 10. Fan-coil electric heat kW
Unit Size
62
Free-discharge motors on units with three- and four-row coils
115 Volt
FLA
hp (kW)
2
0.60
0.03 (0.02)
3
0.80
0.05 (0.04)
4
1.00
0.06 (0.04)
6
1.40
0.12 (0.09)
8
1.70
0.13 (0.10)
10
1.00
0.06 (0.04)
1.40
0.12 (0.09)
12
1.00
0.06 (0.04)
1.70
0.13 (0.10)
High-static motors on units with three- and four-row coils
115 Volt
FLA
hp (kW)
2
1.10
0.07 (0.05)
3
1.30
0.08 (0.06)
4
2.10
0.13 (0.10)
6
3.40
0.24 (0.18)
8
3.40
0.24 (0.18)
10
2.10
0.13 (0.10)
3.40
0.24 (0.18)
12
2.10
0.13 (0.10)
3.40
0.24 (0.18)
Unit Voltage
kW
02
115
1.0
230
1.0
277
1.0
208
0.8
03
115
1.0
230
1.0
277
1.0
208
0.8
04
115
230
277
208
208–230 Volt
FLA
hp (kW)
FLA
0.3
0.03 (0.02)
0.2
0.5
0.05 (0.04)
0.4
0.6
0.06 (0.04)
0.5
0.9
0.12 (0.09)
0.6
1.0
0.13 (0.10)
0.8
0.6
0.06 (0.04)
0.5
0.9
0.12 (0.09)
0.6
0.6
0.06 (0.04)
0.5
1.0
0.13 (0.10)
0.8
208–230 Volt
FLA
hp (kW)
FLA
0.6
0.07 (0.05)
0.5
0.7
0.08 (0.06)
0.5
0.9
0.13 (0.10)
0.7
1.4
0.24 (0.18)
1.1
1.4
0.24 (0.18)
1.1
0.9
0.13 (0.10)
0.7
1.4
0.24 (0.18)
1.1
0.9
0.13 (0.10)
0.7
1.4
0.24 (0.18)
1.1
kW
kW
kW
kW
1.5
2.0
1.5
2.0
1.5
2.0
1.1
1.5
1.9
1.5
2.0
2.5
1.5
2.0
2.5
1.5
2.0
2.5
1.1
1.5
1.9
2.3
2.0
2.5
3.0
2.0
2.5
3.0
2.0
2.5
3.0
1.5
1.9
2.3
277–480 Volt
hp (kW)
H
0.03 (0.02)
980
0.05 (0.04)
1080
0.06 (0.04)
1080
0.12 (0.09)
1080
0.13 (0.10)
1080
0.06 (0.04)
1080
0.12 (0.09)
1080
0.06 (0.04)
1080
0.13 (0.10)
1080
277–480 Volt
hp (kW)
H
0.07 (0.05)
1480
0.08 (0.06)
1500
0.13 (0.10)
1580
0.24 (0.18)
1475
0.24 (0.18)
1475
0.13 (0.10)
1580
0.24 (0.18)
1475
0.13 (0.10 )
1580
0.24 (0.18)
1475
kW
kW
kW
kW
3.0
rpm
M
L
840
655
800
600
800
600
800
600
800
600
800
600
800
600
800
600
800
600
rpm
M
L
1110
865
1355
1110
1375
1240
1285
975
1285
975
1375
1240
1285
975
1375
1240
1285
975
kW
kW
UNT-SVX07B-EN