Vent Clearances And Framing; Pipe Clearances To Combustibles; Wall Penetration Framing/Firestops - Heat & Glo LUX42 Installation Manual

Hide thumbs Also See for LUX42:
Table of Contents

Advertisement

5 5

Vent Clearances and Framing

A. Pipe Clearances to Combustibles
WARNING! Risk of Fire! Maintain air space clearance
to vent. DO NOT pack insulation or other combustibles:
• Between ceiling fi restops
• Between wall shield fi restops
• Around vent system
Failure to keep insulation or other material away from
vent pipe may cause overheating and fi re.
Note: Heat shields MUST overlap by a minimum of 1-1/2 in. (38 mm).
DVP heat shield - designed to be used on a wall 4 in. to 7-1/4 in. (102 mm to 184
mm) thick.
wall thickness is greater than 7-1/4 in. a DVP-HSM-B will be required.
(DVP Pipe Shown)
Heat
Shield
3 in. (76 mm)
top clearance
clearance around
vertical sections
Firestop
Figure 5.1 Horizontal Venting Clearances To Combustible
Materials
26
3 in. (76 mm)
top clearance *
Heat
Shield
clearance
Wall
bottom & sides
Shield
WALL
Heat & Glo • LUX36, LUX42 Installation Manual
B. Wall Penetration Framing/Firestops
Combustible Wall Penetration
Whenever a combustible wall is penetrated, you must
frame a hole for the wall shield fi restop(s). The wall shield
fi restop maintains minimum clearances and prevents cold
air infi ltration.
• The opening must be framed on all four sides using the
same size framing materials as those used in the wall
construction.
• DVP pipe - A wall shield fi restop is required on one side
only on interior walls. If your local inspector requires a
wall shield fi restop on both sides, then both wall shield
fi restops must have a heat shield (refer to Section
12.A.) attached to them.
• See Section 7.F. for information for regarding the instal-
lation of a horizontal termination cap.
Non-Combustible Wall Penetration
If the hole being penetrated is surrounded by non-com-
bustible materials such as concrete, a hole with diameter
one inch greater than the pipe is acceptable.
Whenever a non-combustible wall is penetrated, the wall
shield fi restop is only required on one side and no heat
shield is necessary.
DO NOT PACK WITH
INSULATION OR OTHER
MATERIAL
10 in.
12 in.
A*
MODEL
LUX36 NG
LUX42 NG
* Shows center of vent framing hole with minimum vertical for top venting. The
center of the hole is one (1) in. (25.4 mm) above the center of the horizontal
vent pipe.
Figure 5.2 Wall Penetration
• 2287-980 Rev. L
• 2287-980 Rev. L • 4/16
B
A*
B
74-3/16 in.
73-3/16 in.
103-3/16 in.
102 -3/16 in.

Advertisement

Table of Contents
loading

This manual is also suitable for:

Lux36

Table of Contents