C. Approved Pipe
This appliance is approved for use with Hearth & Home
Technologies DVP venting systems. Refer to Section
12.A for vent component information and dimensions.
DO NOT mix pipe, fi ttings or joining methods from differ-
ent manufacturers.
The pipe is tested to be run inside an enclosed wall.
There is no requirement for inspection openings at each
joint within the wall.
WARNING! Risk of Fire or Asphyxiation. This appli-
ance requires a separate vent. DO NOT vent to a pipe
serving a separate solid fuel burning appliance.
D. Use of Elbows
Diagonal runs have both vertical and horizontal vent as-
pects when calculating the effects. Use the rise for the
vertical aspect and the run for the horizontal aspect. See
Figure 4.4.
Two 45º elbows may be used in place of one 90º elbow.
On 45º runs, one foot of diagonal is equal to 8-1/2 in. (216
mm) horizontal run and 8-1/2 in. (216 mm) vertical run. A
length of straight pipe is allowed between two 45º elbows.
See Figure 4.4.
Figure 4.5 shows the vertical and horizontal offsets for
DVP or SLP elbows.
VERTICAL
Effective Length
DVP
Pipe
Inches
Millimeters
DVP4
4
102
DVP6
6
152
DVP12
12
305
DVP24
24
610
DVP36
36
914
DVP48
48
1219
DVP6A
3 to 6
76 to 152
DVP12A
3 to 12
76 to 305
Figure 4.4
18
RUN
HORIZONTAL
Rise/Run
Inches
Millimeters
2-3/4
70
4-1/4
108
8-1/2
216
17
432
25-1/2
648
34
864
2-1/8-4-1/4
54-108
2-1/8-8-1/2
54-216
Heat & Glo • LUX36, LUX42 Installation Manual
X
X
Vent
Type
Inches
Millimeters
DVP
4-1/2
X
Vent Type
DVP
Figure 4.5 Vertical and Horizontal Offset for DVP and SLP Elbows
E. Measuring Standards
Vertical and horizontal measurements listed in the vent
diagrams were made using the following standards:
• Pipe measurements are shown using the effective length
of pipe. See Section 12.A for information on effective
length of pipe components.
• Horizontal terminations are measured to the outside
mounting surface (fl ange of termination cap) (see Figure
4.3).
• Vertical terminations are measured to bottom of
termination cap.
• Horizontal pipe installed level with no rise.
Note: Model LUX42 (NG) must have 48 inches minimum
vertical vent before attaching any elbow to the appliance.
• 2287-980 Rev. L • 4/16
• 2287-980 Rev. L
Y
Y
Inches
Millimeters
114
17
432
X
X
Inches
Millimeters
16-1/4
413