Top Vent - Vertical Termination
2 ELBOWS
WARNING! Risk of Fire!
• LUX36 requires a minimum of 24 inches of vertical venting before
attaching any elbow to the appliance.
• LUX42 requires a minimum of 48 inches of vertical venting before
attaching any elbow to the appliance.
DO NOT attach elbow directly to the appliance.
Note: Flue restrictor is permit-
ted ONLY on 30 ft. minimum
vertical runs with no elbows.
V
2
Figure 4.10
H
1
Heat & Glo • LUX36, LUX42 Installation Manual
V
1
2 ft
610 mm
3 ft
914 mm
4 ft
1.2 m
5 ft
1.5 m
6 ft
1.8 m
*No specifi c restrictions on this value EXCEPT
V
+ V
1
After V
V
1
4 ft
1.2 m
5 ft
1.5 m
6 ft
1.8 m
*No specifi c restrictions on this value EXCEPT
V
+ V
1
After V
V
1
• 2287-980 Rev. L
2287-980 Rev. L • 4/16
LUX36
H
Maximum
1
17 in.
432 mm
3 ft
914 mm
4 ft
1.2 m
9 ft
2.7 m
12 ft
3.7 m
+ H
= 50 ft (15.2 m) Max.
2
1
= 6 ft, then H
Max.= V
x 2
1
1
1
LUX42
H
Maximum
1
17 in
432 mm
2 ft
610 mm
9 ft
2.7 m
+ H
= 50 ft (15.2 m) Max.
2
1
= 6 ft, then H
Max.= V
x 2
1
1
1
V
2
*
*
*
*
*
V
2
*
*
*