Gas valve selection

The gas pressure loss specified in the
table is to be added on to the combus-
tion chamber pressure in mbar.
G 05.700 MODULO
DMV512-T
Burner
Rp1,1/2
power
Natural gas E Hi = 10.365 kWh/m
(kW)
550
16
600
19
650
22
700
26
G 05.1000 MODULO
DMV512-T
Burner
Rp1,1/2
power
Natural gas E Hi = 10.365 kWh/m³
(kW)
550
17
600
20
650
23
700
27
750
31
800
35
850
40
900
44
950
49
1000
55
1
Example (for Burner G 05.1000 MODULO):
· System data:
Gas type: natural gas E
Gas flow pressure: 20 mbar (N.B.: at gas valve inlet)
Required burner power: 700 kW
Combustion chamber pressure with boiler rated load: 2.5 mbar
· Condition: working point must be within the burner's permissible field of work.
· Selected gas valve: DMV 520-T
· Checking the selection:
Gas pressure loss (from table):
Combustion chamber pressure:
Total
Hence: Gas flow pressure 20 mbar >19.5 mbar ð Selection of DMV520-T correct.
6
N.B.:
The calculated gas flow pressure is to
be complied with at the gas valve inlet.
To calculate the gas flow pressure
required at the transfer station, the
resistance of the burner supply conduit
including valves (ball valve, TAS, addi-
tional filter or counter) must also be
taken into account.
DMV520-T
Rp 2
3
Gas pressure loss (from gas valve inlet)
15
15
18
21
DMV520-T
DMV525-R
Rp 2
Rp 2
Gas pressure loss (from gas valve inlet)
15
15
15
15
15
15
17
15
20
18
23
20
26
23
29
25
32
28
36
31
17
mbar
2.5 mbar
19.5 mbar
09/2005 - Art. Nr. 13 019 526A
DMV512-T
Rp1,1/2
Natural gas LL Hi = 8.83 kWh/m
17
21
24
28
DMV5065-R
DMV520-T
DN65
Rp 2
Natural gas LL Hi = 8.83 kWh/m³
15
15
15
17
15
20
15
24
18
27
20
31
23
35
25
39
28
44
31
48
DMV520-T
Rp 2
3
15
16
19
22
DMV525-R
DMV5065-R
Rp 2
DN65
15
15
15
15
17
17
20
20
23
23
26
26
29
29
33
33
37
37
41
41
DMV512-T
Rp1,1/2
Propane gas
Hi=25.89kWh/m³
15
15
17
20
DMV512-T
Rp1,1/2
Propane gas
Hi=25.89kWh/m³
15
15
16
18
21
24
27
30
34
38

Advertisement