Start-Up; Default Settings - elco VECTRON G 05.700 MODULO Operating Instructions Manual

Table of Contents

Advertisement

Start-up

Default settings

Natural gas settings table G 05.700 MODULO
Burner power
Low load
Rated load
kW
kW
140
400
150
500
160
600
170
700
Natural gas settings table G 05.1000 MODULO
Burner power
Low load
Rated load
kW
kW
170
600
170
700
200
800
220
900
250
1000
The above setting data are basic settings. The factory setting data are in boxes with thick black borders. The burner can
normally be run using these settings. Check the setting values carefully in each case. System-specific corrections may be
necessary.
Propane gas settings table G 05.700 MODULO
Burner power
Dimension
Low load
Rated load
kW
kW
140
400
150
500
160
600
170
700
Propane gas settings table G 05.1000 MODULO
Burner power
Dimension Y
Low load
Rated load
kW
kW
170
600
170
700
200
800
220
900
250
1000
18
Dimension
Air flap opening
Y
Ignition
Low load
load
P0 (°)
mm
10
0
20
0
35
5
40
5
Dimension
Air flap opening
Y
Ignition
Low load
load
P0 (°)
mm
20
0
25
2
30
6
35
8
40
9
Air flap opening
Y
Ignition
Low load
load
P0 (°)
mm
10
4
20
4
30
4
40
4
Air flap opening
Ignition
Low load
load
mm
P0 (°)
15
6
20
6
25
7
35
7
40
8
09/2005 - Art. Nr. 13 019 526A
Rated load
Ignition
P1 (°)
P9 (°)
load
P0 (°)
0
25
0
29
5
40
5
45
24.5
Rated load
Ignition
P1 (°)
P9 (°)
load
P0 (°)
0
38
26.5
2
41
26.5
6
68
8
68
9
68
Rated load
Ignition
P1 (°)
P9 (°)
load
P0 (°)
4
20
19
4
29
19
4
36
19
4
40
19
Rated load
Ignition
P1 (°)
P9 (°)
load
P0 (°)
6
36
19.5
6
63
19.5
7
63
19.5
7
68
19.5
8
68
22
Gas throttle opening
Low load
Rated load
P1 (°)
P9 (°)
23
23
39
23
23
43
24
24
50
24.5
62
Gas throttle opening
Low load
Rated load
P1 (°)
P9 (°)
26.5
56
26.5
65
27
27
90
28
28
90
29
2
90
Gas throttle opening
Low load
Rated load
P1 (°)
P9 (°)
19
30.5
19
36
19
41
19
45
Gas throttle opening
Low load
Rated load
P1 (°)
P9 (°)
19.5
42
19.5
75
19.5
75
19.5
75
22
75
Pressure
adjustment
setting
pVA mbar
15
15
15
15
Pressure
adjustment
setting
pVA mbar
15
15
18.5
18.5
18.5
Pressure
regulator
setting
pVA mbar
15
15
15
15
Pressure
regulator
setting
pVA mbar
17.5
17.5
17.5
17.5
17.5