Start-up
Adjustment mode
Cold adjustment menu: Burner pre-adjustment
Full load
Air: .. ` .
Next
?
Low load
Air: .. ` .
Next
?
Ignition load
Air: .. ` .
Next
?
Burner via boiler
regulator for hot adj
start adjustment
?
Cold adjustment (with ball valve closed)
In the "Cold adjustment" menu item, the P9/P1/P0 key data are pre-adjusted in
accordance with the setting table (page 18) for the desired burner power.
The control unit then calculates the intermediate points P2 to P8 and switches to
the "Hot adjustment" menu.
· Accessing the adjustment mode.
· Select cold adjustment with
· Confirm with
Adjust air and gas setting.
· Position the cursor on air or gas with
P9
· Activate with
Gas: ..´ .
· Set new value with
· Confirm with
Switch between adjustment points P9/P1/P0.
P1
· Position cursor on "Next" or "Back" with
Gas: ..´ .
· Confirm with
Back
· If the position "Next" is confirmed for adjustment point P0 with
control unit calculates the intermediate points P2 to P8 and then switches to
the hot adjustment menu .
Direct access to this menu via adjustment mode/hot adjustment
P0
Gas: ..´ .
Back