Start-up
Adjustment mode
Parameters menu: programming of additional functions
Rest pos. Air flap
00.0°
Next
Delete error list
Next
Check for leak
Y
Next
Valve 1 check time
006s
Next
Valve 2 check time
006 s
Next
Address Regulation
10H
Next
Connection setup
Save parameters
Control unit unprogrammed
22
This parameter allows you to adjust the rest position of the air flap.
–
This parameter (in degrees) may be required after reventilation.
Default setting 00.0°
Back
With this function, accumulated errors are deleted from the error log
–
(display information: "Empty"). The next new error is written under
No. 0 in the error log.
Back
Leak check:
–
With this function, you can deactivate the valve leak check.
Back
Valve 1 check time:
–
For proper execution of the leak check, at least the 6 seconds set in the
factory are required.
Adjustment range: 1-240 s
Back
Valve 2 check time:
–
For proper execution of the leak check, at least the 6 seconds set in the
factory are required.
Adjustment range: 1-240 s
Back
Address regulation (factory setting to 10H)
–
Other addresses are possible: F7H, F0H, 77H, 70H, 37H, 30H, 17H.
Back
After confirming "Next" in the "Address regulation" menu item, the newly
–
adjusted parameters are saved in the control unit. The control unit then
switches back to "Ready for operation".
09/2005 - Art. Nr. 13 019 526A
Y= Yes/N= No