Assembly
Checking/Setting
Mixer unit for natural gas/propane gas
16
Checking the mixing unit
· Check and adjust the setting of the
ignition electrodes and the
turbulator.
1
Fitting the mixing unit
· Release and remove the mixing unit
cover by unscrewing the three Allen
screws 1.
· Check the gas connection O-ring.
· Fit the mixing unit and tighten with
screw at side (M10 counter nut and
Allen screw).
· Fit the extension rod with 0-40 scale
(loose in accompanying pack) for
setting the turbulator.
· The extension rod must be pushed
into the steel sleeve until it makes
contact.
09/2005 - Art. Nr. 13 019 526A
Recommended setting for natural gas
On the gas diffusers labelled A, 5
outwards-facing slots and 1
inwards-facing slot should be left
covered by sleeve E.
Secure the turbulator with 6 drilled
M5x6 screws F.
On the gas diffusers labelled B, 5
outwards-facing slots and 0
inwards-facing slots should be left
covered by sleeve E.
Recommended setting for propane gas
On the gas diffusers labelled C, 2
outwards-facing slots and 1
inwards-facing slot should be left
covered by sleeve E.
Secure the turbulator with 5 solid
M5x6 screws (diffuser D) and 1 drilled
M5x6 screw F (diffuser C).
On the gas diffusers labelled D, 2
outwards-facing slots and 0
inwards-facing slots should be left
covered by sleeve E.
· Feed ignition cable 2 and ionisation
cable 3 through the opening and
push in the rubber bushing.
· Screw down the cover, connect the
ignition cables 2 and ionisation
cable 3.