Control unit
(cont.)
Heating mode
The control unit calculates a set boiler
water temperature depending on the
outside temperature and/or the room
temperature (if a room temperature-
controlled remote control facility is
connected) and the slope/level of the
heating curve. The determined set
boiler water temperature is then trans-
ferred to the burner control unit.
DHW heating
The burner, the circulation pump and
the three-way valve are started or
changed over, if the cylinder tempera-
ture lies 2.5 K below the set cylinder
temperature.
Boosting DHW heating
The booster heating function is acti-
vated if a switching period is selected
for the fourth time phase.
Function description
The burner control unit calculates the
heat demand and controls the two-
stage burner accordingly. The burner
control unit limits the boiler water tem-
perature: to 74 °C by the temperature
controller, and to 82 °C by the electro-
nic temperature limiter. The tempera-
ture limiter of the safety chain locks
out the burner control unit at a boiler
water temperature of 100 °C.
The set boiler water temperature is
adjusted 20 K higher than the set
DHW temperature (adjustable via
coding address "60"). The burner will
be switched OFF and the circulation
pump run-on time will begin, if the
actual cylinder temperature exceeds
the set cylinder temperature by 2.5 K.
The set temperature value for the
heating boost is adjustable in coding
address "58".
83