Viessmann VITOLADENS333-F Service Instructions Manual page 71

Type vp3s, 12.9/19.3 kw, 16.1/23.5 kw oil fired compact condensing boiler, for the combustion of low sulphur fuel oil din 51603-el-1
Table of Contents

Advertisement

Fault codes
(cont.)
Fault code
System character-
on the dis-
istics
play
C7
Control mode, max.
pump speed
Cd
Control mode
CE
Control mode
CF
Control mode
dA
Control mode with-
out room influence
db
Control mode with-
out room influence
dd
Control mode with-
out room influence
dE
Control mode with-
out room influence
E4
Burner blocked
Cause
Measures
Communication
Check the setting of
fault
external
coding address "E5".
variable speed
heating circuit
pump, heating
circuit A1
Communication
Check connections,
fault Vitocom 100
Vitocom 100 and coding
(KM BUS)
address "95".
Communication
Check connections and
fault
ext. exten-
coding address "2E".
sion
Communication
Replace the LON com-
fault, LON com-
munication module.
munication mod-
ule
Room tempera-
Check the room tem-
ture sensor, heat-
perature sensor, heating
ing circuit A1
circuit A1.
shorted out
Room tempera-
Check the room tem-
ture sensor, heat-
perature sensor, heating
ing circuit with
circuit with mixer M2.
mixer M2 shorted
out
Room tempera-
Check the room tem-
ture sensor, heat-
perature sensor, heating
ing circuit A1 lead
circuit A1 and the re-
broken
mote control DIP switch
settings (see page 93).
Room tempera-
Check the room tem-
ture sensor, heat-
perature sensor, heating
ing circuit with
circuit with mixer M2
mixer M2 lead
and the remote control
broken
DIP switch settings (see
page 93).
Supply voltage
Replace the control unit.
fault
Troubleshooting
71