Viessmann VITOLADENS333-F Service Instructions Manual page 57

Type vp3s, 12.9/19.3 kw, 16.1/23.5 kw oil fired compact condensing boiler, for the combustion of low sulphur fuel oil din 51603-el-1
Table of Contents

Advertisement

Code 2
(cont.)
Coding in the delivered condition
b0:0
With remote control:
Heating mode/reduced
mode: weather-com-
pensated (change cod-
ing only for the heating
circuit M2 with mixer)
b2:8
Heating with room tem-
perature hook-up must
be programmed for re-
mote control and for the
heating circuit: Room
influence factor 8
(change coding only for
the heating circuit M2
with mixer)
b5:0
With remote control: No
room temperature-de-
pendent heating circuit
pump logic function
(change the coding only
for the heating circuit
with mixer M2)
Parameter ad-
With heating circuit pump logic function: Heating cir-
dress b5: ...
cuit pump OFF, if
1:
enabled RT
2:
enabled RT
3:
enabled RT
4:
enabled RT
5:
enabled RT
6:
enabled RT
Possible change
b0:1
b0:2
b0:3
b2:0
b2:1
to
b2:64
b5:1
to
b5:8
> RT
+ 5 K; disabled RT
actual
set
> RT
+ 4 K; disabled RT
actual
set
> RT
+ 3 K; disabled RT
actual
set
> RT
+ 2 K; disabled RT
actual
set
> RT
+ 1 K; disabled RT
actual
set
> RT
; disabled RT
actual
set
Coding
Heating mode: weather-
compensated
Reduced mode: with
room temperature hook-
up
Heating mode: with room
temperature hook-up
Reduced mode: weather-
compensated
Heating mode/reduced
mode: with room tem-
perature hook-up
Without room influence
Room influence factor
adjustable from 1 to 64
Heating circuit pump
logic function, see the fol-
lowing table:
< RT
+ 4 K
actual
set
< RT
+ 3 K
actual
set
< RT
+ 2 K
actual
set
< RT
+ 1 K
actual
set
< RT
actual
set
< RT
- 1 K
actual
set
57