Viessmann VITOLADENS333-F Service Instructions Manual page 72

Type vp3s, 12.9/19.3 kw, 16.1/23.5 kw oil fired compact condensing boiler, for the combustion of low sulphur fuel oil din 51603-el-1
Table of Contents

Advertisement

Troubleshooting
Fault codes
(cont.)
Fault code
System character-
on the dis-
istics
play
E5
Burner in a fault
state
E6
Burner in a fault
state
F0
Burner blocked.
F1
Burner in a fault
state
F2
Burner in a fault
state
F3
Burner in a fault
state
F4
Burner in a fault
state
72
Cause
Measures
Internal fault
Press "E RESET".
Replace the control unit
if the burner will not re-
start.
The oil preheater
Check oil pre-heater and
does not respond
supply line and replace
inside the toler-
if necessary.
ated time
Press "E RESET".
Internal fault
Replace the control unit.
Flue gas tem-
Check the heating sys-
perature limiter
tem fill level. Vent the
has responded
system.
Press "E RESET" after
the flue gas system has
cooled down.
The temperature
Check the heating sys-
limiter has re-
tem fill level. Check the
sponded
circulation pump. Vent
the system. Check the
temperature limiter and
connecting cables.
Press "E RESET".
Flame signal is al-
Check ignition electro-
ready present at
des, electrode gaps and
burner start
connecting lines.
Press "E RESET".
The flame is not
Check oil supply, igni-
established at the
tion electrodes, elec-
end of the safety
trode gaps and
time
connecting lines,
check nozzle, check so-
lenoid valve coil.
Correct all settings, if re-
quired; clean all con-
taminated parts and
replace faulty compo-
nents.
Press "E RESET".