Viessmann VITOLADENS333-F Service Instructions Manual page 21

Type vp3s, 12.9/19.3 kw, 16.1/23.5 kw oil fired compact condensing boiler, for the combustion of low sulphur fuel oil din 51603-el-1
Table of Contents

Advertisement

Further details regarding the individual steps
Rated output
Nozzle gap "a" (see page 20)
Commissioning, inspection, maintenance
(cont.)
2. Insert a new LE nozzle E (whilst
holding the oil preheater).
Select the nozzle in accordance
with the details on page 15.
!
Please note
Only use nozzles marked
"V" (on the hexagon) (see
Fig.).
3. Insert rifling facility D as far as
possible. Align ignition electrodes
B in accordance with the drilled
holes towards the cable entries.
Install the oil burner nozzle cen-
trally into the restrictor.
4. Secure Allen screw C of the rifling
facility. Check nozzle gap "a".
!
Please note
An incorrectly adjusted noz-
zle gap "a" can result in irre-
gular operation of the burner
and even a fault shutdown.
kW
12.9/19.3
+0.2/-0.3
mm
3.0
16.1/23.5
+0.2/-0.3
1.5
21

Advertisement

Table of Contents
loading

Table of Contents