Troubleshooting
Fault codes
(cont.)
Fault code
System character-
on the dis-
istics
play
b4
Regulates as if the
outside temperature
was 0 °C
b5
Control mode as per
delivered condition
b7
Burner blocked.
b8
Burner blocked
bA
Mixer M2 regulates
to a flow tempera-
ture of 20 °C.
bC
Control mode with-
out remote control
bd
Control mode with-
out remote control
bE
Control mode
bF
Control mode
C5
Control mode, max.
pump speed
C6
Control mode, max.
pump speed
70
Cause
Measures
Internal fault
Replace the control unit.
Internal fault
Replace the control unit.
Boiler coding card
Plug in boiler coding
missing, faulty or
card or replace it, if
incorrect boiler
faulty.
coding card
Flue gas tem-
Check the flue gas tem-
perature sensor
perature sensor (see
lead broken
page 77).
Communication
Check the extension kit
fault
extension
connections and coding.
kit for heating cir-
Start the extension kit.
cuit M2
Communication
Check connections,
fault
Vitotrol re-
cable, coding address
mote control,
"A0" and the remote
heating circuit A1
control DIP switches.
Communication
Check connections,
fault, Vitotrol re-
cable, coding address
mote control,
"A0" and the remote
heating circuit M2
control DIP switches.
Vitotrol remote
Check remote control
control incorrectly
DIP switch settings (see
programmed
page 93).
Incorrect LON
Replace the LON com-
communication
munication module.
module
Communication
Check the setting of
error
variable
coding address "30"
speed internal cir-
culation pump
Communication
Check the setting of
fault
external
coding address "E5".
variable speed
heating circuit
pump, heating cir-
cuit with mixer M2