Viessmann VITOLADENS333-F Service Instructions Manual page 50

Type vp3s, 12.9/19.3 kw, 16.1/23.5 kw oil fired compact condensing boiler, for the combustion of low sulphur fuel oil din 51603-el-1
Table of Contents

Advertisement

Coding
Code 2
(cont.)
Coding in the delivered condition
DHW
56:0
Set DHW temperature
adjustable from 10 to
60 °C
58:0
Without auxiliary func-
tion for DHW heating
59:0
Cylinder heating:
Starting point -2.5 K
Stopping point +2.5 K
60:20
During DHW heating,
the boiler water tem-
perature is max. 20 K
higher than the set
DHW temperature
62:2
Circulation pump with
2 min run-on time after
cylinder heating
65:...
Information regarding
the type of diverter
valve. Do not adjust
6C:100
Set speed; internal cir-
culation pump with
DHW heating 100 %
50
Possible change
56:1
Set DHW temperature
adjustable from 10 to
above 60 °C
Note
Maximum value subject
to boiler coding card.
Observe the max. per-
missible DHW tempera-
ture.
58:10
Input of a second set
to
DHW temperature, adjus-
58:60
table from 10 to 60 °C
(observe coding ad-
dresses "56" and "63")
59:1
Starting point adjustable
to
from 1 to 10 K below the
59:10
set value
60:5
The difference between
to
the boiler water tempera-
60:25
ture and the set DHW
temperature is adjustable
from 5 to 25 K
62:0
Circulation pump without
run-on
62:1
Run-on time adjustable
to
from 1 to 15 min
62:15
65:0
Without diverter valve
65:1
Diverter valve by
Viessmann
65:2
Diverter valve by Wilo
65:3
Diverter valve by Grund-
fos
6C:0
Set speed adjustable
to
from 0 to 100 %
6C:100