Fault codes
(cont.)
Fault code
System character-
on the dis-
istics
play
F5
Burner in a fault
state
F7
Burner in a fault
state
F8
Burner in a fault
state
F9
Burner in a fault
state
F9
Burner in a fault
state
FA
Burner in a fault
state
Fb
Burner in a fault
state
Fd
Burner blocked
Cause
Measures
The air pressure
Check air pressure
switch does not
switch and replace if ne-
respond.
cessary.
Press "E RESET".
No control/feed-
Replace fuel valve BV 2
back of/from fuel
Press "E RESET".
valve BV 2
Fuel valve BV 1
Check nozzle, vent oil
closes late
supply line, check sole-
noid valve
Press "E RESET".
Fan speed too
Check the fan, check
low during the
the fan connecting
burner start
cables, check the fan
power supply.
Press "E RESET".
Fan power supply
Check fire safety switch
is interrupted
or smoke thermostat,
The fire safety
check jumper across
switch or flue
terminals 1 and 2 in
gas thermostat
junction box 201 (see
is faulty or has
page 97).
responded
Press "E RESET".
The jumper
across term-
inals 1 and 2 in
junction box
201 is broken or
has been
removed
Fan speed devia-
Check fan, check con-
tion
necting cables to fan.
Press "E RESET".
3 x flame blow-off
Check oil supply, check
during operation
nozzle.
Press "E RESET".
Burner control
Press "E RESET" . Re-
unit fault
place control unit if the
fault persists