19 DETERMININg ThE FLUE LENgTh aND FLUE paCKs REqUIRED........CONT'D
90º Elbow Kit 60/100 - (Equivalent flue length resistance = 1M)
45º Elbow Kit 60/100 - (Equivalent flue length resistance = 0.6M)
Minimum horizontal Flue Lengths (Centre line of turret to outside of wall terminal)
Telescopic Flue 'B' Pack = 400mm
Horizontal Flue terminal (600mm long) 'B' Pack = 285mm
Wall Thickness
'B' Pack Flue Type 60/100
Horizontal Flue Terminal
(600mm long) B Pack
Telescopic Flue B Pack
Horizontal Flue Terminal
(1000mm long) B Pack
Horizontal Flue Terminal
(1000mm long) B Pack cut 75mm
For Flue lengths between 658 & 708 use a horizontal Flue Terminal (1000mm long) B pack, cut 75mm off the end of the
terminal section of the telescopic flue only.
20 DETERMININg ThE FLUE LENgTh aND FLUE paCKs REqUIRED, CONT'D
FIgURE 1
Note. Maximum permissible
flue length is measured from
centre line of appliance flue
outlet to outside wall face.
FIgURE 2
Shows the flue required when measured from outside edge of turret to the outside face of the wall (to obtain cut length add 44mm)
horizontal Flue Terminal
(600mm long) B pack
Minimum
B pack (standard)
Plus 1 (1m D pack)
Plus 2 (1m D pack)
Plus 3 (1m D pack)
Plus 4 (1m D pack)
Plus 5 (1m D pack)
Plus 6 (1m D pack)
Plus 7 (1m D pack)
Plus 8 (1m D pack)
Plus 9 (1m D pack)
Note; Telescopic flue B Pack or attached "D" pack extensions do not need to be cut between minimum and maximum values shown above (except
where specified). Horizontal Flue Terminal (600mm long) B Pack flue will require cutting on values below maximum values shown in the table above.
20
INSTALLATION
Std Metric Brick 102.5mm wide
Minimum permissible Wall Thickness
Rear Flue
116
231
546
471
Edge of turret
to outside face of wall plus
44mm = ue length
100mm
REAR
Fit
to wall
NOTES
Centre of turret to edge of turret = 100mm
Turret has a ue insertion of 30mm
The compressed outer wall seal has protruding wall to seal mounting lip - 14mm
From centreline of turret to wall. Rear mount 155mm, side (including clearance) 200mm
Minimum & Maximum finished flue lengths obtainable (dimension 'A' +44mm)
Telescopic Flue B pack
Maximum
Minimum
171
556
286
1121
1506
1236
2071
2456
2186
3021
3406
3136
3971
4356
4086
4921
5306
5036
5871
6256
5986
6821
7206
6936
7771
8156
7886
8721
9000
8836
Maximum permissible Wall Thickness
side Flue
Rear Flue
102.5
186
501
426
A
Minimum clearance 5mm
horizontal Flue
Terminal (1000mm long)
B pack (Telescopic)
Maximum
Minimum
484
601
1434
1551
2384
2501
3334
3451
4284
4401
5234
5351
6184
6301
7134
7251
8084
8201
9000
9000
side Flue
501
456
429
384
761
716
686
641
Edge of turret
to outside face of wall plus
44mm = ue length
A
SIDE
Fit
to wall
Flue length measured from outer terminal lip
to end of outer ue
A + 44mm
horizontal Flue Terminal
(1000mm long) B pack
(Telescopic) Cut 75mm
Maximum
Minimum
Maximum
816
526
1766
1476
2716
2426
3666
3376
4616
4326
5566
5276
6516
6226
7466
7176
8416
8126
9000
9000
Project Heat -
Installation and Servicing
741
1691
2641
3591
4541
5491
6441
7391
8341
9000