Flue Terminal Position - IDEAL Project Heat 15 Installation And Servicing

Table of Contents

Advertisement

30 FLUE TERMINaL pOsITION

The terminal should be positioned so that products of
combustion can safely disperse at all times.
pluming may occur at the termination so, where possible,
terminal positions where this could cause a nuisance
should be avoided.
Minimum dimensions are shown below
300mm
min
Flat roof - with structure
A = 600mm
B = 2000mm
The flue terminal shall not penetrate the shaded area of the roof
Terminal position
Directly below an opening,
air brick, windows, etc.
Below plastic / painted gutters
Painted surface
Below eaves or balcony
Below velux windows
Above or side of velux windows
Project Heat -
Installation and Servicing
INSTALLATION
m
0 m
3 0
i n
m
625mm
Fixed
A
A
A
B
Minimum Dimension
300 mm
300 mm
300 mm
500 mm
2000mm
600mm
3 0 0 m m
m i n
690mm
Fixed
Note.
The equivalent flue length
resistance of the elbow kits are:
90
elbow kit = 1m
o
45
elbow kit = 0.6m
o
27