Polarity Reversal Of Solar Module Strings; Overview - Fronius IG Plus A 3.0-1 UNI Operating Instructions Manual

Inverter for grid-connected photovoltaic systems
Table of Contents

Advertisement

Polarity Reversal
of Solar Module
Strings
Connecting all solar module strings with reverse polarity will not cause any damage to the
inverter.
All solar module strings connected with reverse polari-
ty - no damage to the inverter

Overview

'Connecting solar module strings to the inverter (DC)' includes the following sections:
-
-
-
-
-
-
42
CAUTION! Risk of damage and fire to inverter due to reverse polarity of single
solar module strings.
Reverse polarity of even one single solar module string can cause an unaccept-
able thermal load, which can lead to an inverter fire.
Confirm string polarity and voltage before connecting DC wires to the inverter!
DC+ DC-
-
-
-
Connecting solar module strings
Criteria for the proper selection of string fuses
Connecting combined solar module strings using connecting distributors
Solar module ground at positive pole: Connecting solar module strings
Criteria for the proper selection of string fuses
Solar module ground at positive pole: Connecting combined solar module strings us-
ing connecting distributors
-
+
+
+
-
+
One single solar module string connected with reverse
polarity - risk of damage, risk of fire !